Part name | Check method and criterion | Figure |
Measure the resistance with a tester. (Part temperature
Defrost |
| Normal |
| Abnormal |
|
| |
thermistor |
|
|
|
| |||
|
|
|
|
|
|
| |
(RT63) |
| 5kΩ ~ 60kΩ | Open or |
|
| ||
|
|
|
| ||||
Compressor | Measure the resistance between the terminals with a tester. |
|
| ||||
(MC) | (Coil wiring temperature |
|
| WHT C | |||
INNER |
|
| |||||
|
|
|
|
|
|
| |
PROTECTOR |
|
| Normal |
|
|
| P |
|
|
| Abnormal | AUX. MAIN | |||
|
|
|
| ||||
150i 5°C OPEN |
|
|
| ||||
|
| S | RBLK | ||||
90i10°C CLOSE |
|
|
|
|
| ||
3.41~4.18Ω | 2.99~3.67Ω | 2.46~3.01Ω |
|
| RED | ||
Open or |
|
| |||||
155i 5°C OPEN | 5.41~6.63Ω | 4.02~4.92Ω | 2.96~3.63Ω |
|
| ||
|
|
| |||||
90i10°C CLOSE |
|
|
| ||||
|
|
|
|
|
|
|
Outdoor fan | Measure the resistance between the terminals with a tester. |
| ||||
(Coil wiring temperature |
|
| ||||
motor |
|
| ||||
|
|
|
| MAIN | ||
(MF) |
|
|
|
| ||
Color of | Normal | Abnormal | AUX. | |||
| ||||||
| lead wire |
| ||||
INNER FUSE |
| FUSE | ||||
|
| |||||
145i 2°C | 323 ~ 396 Ω | 189 ~ 233 Ω | Open or |
| ||
CUT OFF | 241 ~ 296 Ω | 270 ~ 332 Ω |
| |||
| BLK RED WHT | |||||
|
|
10-4. Troubleshooting flow
Compressor and/or outdoor fan motor doesn’t operate.
P INNER PROTECTOR
A Check of outdoor unit
Start |
|
|
| |
|
|
|
|
|
|
|
|
|
|
Is the switch SW2- on the | No |
| ||
Change the switch | ||||
indoor electronic control |
|
| on the indoor electronic control | |
|
| |||
P.C. board set to MUH type? |
|
| P.C. board to MUH type. | |
| Yes |
|
|
|
|
|
|
|
|
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
Test run operation operates for 30 minutes.
Compressor doesn't operate.
Is there 5V DC between J205 + | on |
|
| No | Is there 230V AC between 4 on the | ||||||||||||||||
|
|
|
|
|
| compressor contactor (52C) and | |||||||||||||||
the deicer P.C. board? |
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
| TAB20 on the deicer P.C. board? | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Yes | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Is there 230V AC between 3 on the | No | Replace the |
|
| Replace the |
| |||||||||||||||
compressor contactor (52C) and | deicer P.C. |
|
|
| |||||||||||||||||
|
|
|
|
| deicer P.C. board. |
| |||||||||||||||
on the outdoor terminal block (TB1)? |
|
|
| board. |
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Check the compressor and compressor |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| capacitor, and rectify the connecting wire. |
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Outdoor fan motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| doesn't operate. |
|
|
|
|
|
|
| No | Is there 230V AC between 4 on the | ||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||
| Is there 5V DC between J205 + |
|
| ||||||||||||||||||
|
|
|
|
|
|
| compressor contactor (52C) and | ||||||||||||||
| the deicer P.C. board? |
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
| TAB 20 on the deicer P.C. board? | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
| Yes | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| Check the outdoor fan motor |
|
|
|
|
|
|
|
|
|
|
| Replace the |
| ||||||
|
| and rectify the connecting |
|
|
|
|
|
|
|
|
|
|
| deicer P.C. board. |
| ||||||
|
| wire. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
No
No
Rectify the indoor and outdoor connecting wire.
No
Is there 230V AC between –
on the outdoor terminal block (TB1)?
Yes
Rectify the connecting wire.
Rectify the indoor and outdoor connecting wire.
No
Is there 230V AC between – on the outdoor terminal block (TB1)?
Yes
Rectify the connecting wire.