Pioneer MUH-GA25VB, MUH-GA35VB, MUH-GA20VB B Check of outdoor unit, C Check of R.V. coil

Models: MUH-GA20VB MUH-GA25VB MUH-GA35VB

1 36
Download 36 pages 25.9 Kb
Page 25
Image 25
B Check of outdoor unit

Compressor and/or outdoor fan motor doesn’t stop.

B Check of outdoor unit

Start

Turn OFF the power supply. After 1 minute, turn ON power supply again.

No

Does compressor stop?

Yes

OK

No

Does outdoor fan motor stop?

Yes

OK

Is there 230V AC between 3 on the

No

compressor contactor (52C) and N on the

 

 

outdoor terminal block (TB1)?

 

 

Yes

 

 

 

Replace the

 

 

deicer P.C. board.

 

 

 

 

 

 

 

Replace the

 

 

deicer P.C. board.

 

 

 

 

 

 

Rectify the connecting wire.

Unit operates COOL mode even if it is set to HEAT mode.

wFirst, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.

 C Check of R.V. coilManual background C Check of R.V. coil

Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.

After 3 minutes, does the unit operate in COOL mode?

Manual background Yes

Is there 230V AC between CN7211 2 on the deicer P.C. board?

Manual background Yes

Replace the R.V. coil.

No

No

OK

Replace the deicer P.C. board

Unit operates HEAT mode even if it is set to COOL mode.

wFirst, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.

Manual backgroundManual background C Check of R.V. coil

Turn ON the power supply and operate the indoor unit in COOL mode by pressing the EMERGENCY OPERATION switch.

Manual background Yes

After 3 minutes, does the unit operate in HEAT mode?

Manual background Yes

Is there 230V AC between CN7211 2 on the deicer P.C. board?

Manual background Yes

Replace the deicer P.C. board.

No

Ok

No

Replace the R.V. coil.

25

Page 25
Image 25
Pioneer MUH-GA25VB, MUH-GA35VB, MUH-GA20VB service manual B Check of outdoor unit, C Check of R.V. coil