When OPERATION INDICATOR lamp flashes
E Check of outdoor thermistor
Start
Turn OFF the power supply.
Defrost thermistor (RT61)
Measure resistance between CN 661
1and 2.
Is the resistance of Yes thermistor normal?
No
Replace the thermistor.
Reconnect CN661. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Replace the deicer P.C. board.
No
Does the unit operate 10 minutes or more?
Yes
OK ❈
❈Defective contact of the connector is considered.
27