Pioneer MUH-GA25VB liquid, R410A tools, Can R22 tools be used?, Description, Refrigerant piping

Models: MUH-GA20VB MUH-GA25VB MUH-GA35VB

1 36
Download 36 pages 25.9 Kb
Page 4
Image 4
liquid

Conversion chart of refrigerant temperature and pressure

(MPa [Gauge])

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

R410A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

 

 

 

 

R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Saturated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-30 -20

-10 0 10 20 30 40 50 60

NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).

The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f [Gauge])

(:)

1.Tools dedicated for the air conditioner with R410A refrigerant

The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.

The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.

R410A tools

Can R22 tools be used?

Description

 

 

R410A has high pressures beyond the measurement range of existing

Gauge manifold

No

gauges. Port diameters have been changed to prevent any other refrigerant

 

 

from being charged into the unit.

 

 

 

Charge hose

No

Hose material and cap size have been changed to improve the pressure

resistance.

 

 

Gas leak detector

No

Dedicated for HFC refrigerant.

 

 

 

Torque wrench

Yes

6.35 mm and 9.52 mm

 

 

 

Flare tool

Yes

Clamp bar hole has been enlarged to reinforce the spring strength in the tool.

 

 

 

Flare gauge

New

Provided for flaring work (to be used with R22 flare tool).

 

 

 

Vacuum pump

New

Provided to prevent the back flow of oil. This adapter enables you to use

adapter

vacuum pumps.

 

Electronic scale for

New

It is difficult to measure R410A with a charging cylinder because the

refrigerant charging

refrigerant bubbles due to high pressure and high-speed vaporization

 

 

 

 

No : Not Substitutable for R410A Yes : Substitutable for R410A

2.Refrigerant piping

1Specifications

Use the refrigerant pipes that meet the following specifications.

Pipe

Outside diameter

Wall

Insulation material

 

mm

thickness

 

 

 

 

 

 

For liquid

6.35

0.8 mm

Heat resisting foam plastic

For gas

9.52

0.8 mm

Specific gravity 0.045 Thickness 8 mm

 

 

 

 

Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.

4

Page 4
Image 4
Pioneer MUH-GA25VB, MUH-GA35VB, MUH-GA20VB liquid, R410A tools, Can R22 tools be used?, Description, Refrigerant piping