Planar UR8450-MX, UR8450-LX, UR8450-3D manual RS232 Commands, RS232 Command Format

Models: UR8450-LX UR8450-3D UR8450-MX

1 120
Download 120 pages 23.06 Kb
Page 80
Image 80

RS232 Commands

RS232 Commands

The RS232 connection must use the following settings:

19200 baud rate

8 data bits

1 stop bit

No parity bit

No HW (RTS/CTS) or SW (XON/XOFF) flow control

RS232 Command Format

Commands sent from the initiator to the follower must have the following format:

(www:xyz) [CR]

Where:

‘(‘ and ‘)’ indicate the start and end of the command data. If these characters are present, the display processor shall assume that “valid” display data is present in the command string. If these characters are not present in the command, the display processor shall assume the data is not valid display data and ignore it.

“www” indicates the command code. This field is case insensitive (i.e. “PWR”, “pwr” and “PwR” should all be treated as “PWR”).

“:x” is the destination parameter. This is an optional parameter that indicates which memory the command is referencing. This parameter is reserved and shall not be used at this time.

“y” is the operand, which can have one of the following values:

‘?’ = “Get” operand

‘=’ = “Set” operand

‘+’ = “Increment” operand (not supported on UltraRes)

‘-‘ = “Decrement” operand (not supported on UltraRes)

“z” is the value to set for this parameter. It can have one of two formats:

Integer value: Any positive or negative number (example: 100)

String value: Any string surrounded by double quotes (example: “This is a string”)

“[CR]” is the ASCII carriage return key (0x0D).

74

Planar UltraRes User Manual

Page 80
Image 80
Planar UR8450-MX, UR8450-LX, UR8450-3D manual RS232 Commands, RS232 Command Format