Installation

Mounting the UPS in a 19” Rack

Use the following procedure to install the UPS in 19rack configuration:

1.Place the UPS on a flat, stable surface with the front of the UPS facing toward you.

2.On each side of the UPS, attach the long end of a mounting bracket to the UPS using four of the supplied M3￿l 6 screws (see Figure 2).

Mounting Bracket

M3 l 6 Bracket Screws

Figure 2. Mounting Bracket for a 19” Rack

3.Loosen the assembly wing nuts on both rail assemblies and adjust the rail size for the depth of your rack (see Figure 3).

4.Position the rear hold-down bracket toward the end of the rail assemblies where the end of the UPS will be located and tighten the wing nut.

Rear Hold-Down Bracket

Rear

Front

 

Assembly

Wing Nut for Rear

Wing Nuts

Rail Assembly

Hold-Down Bracket

Figure 3. Adjusting the Rail Depth

5.Select the proper holes in the rail for positioning the UPS in the desired location in the rack.

6.Using two M6 l 10 screws and two clip nuts, attach the rail to the rear of the rack (see Figure 4).

20