Specifications

Table 7. Battery

Configuration

500 VA: (2) 6V, 9 Ah internal battery

 

750 VA: (4) 6V, 7.2 Ah internal batteries

 

1000 VA: (4) 6V, 9 Ah internal batteries

 

1500 VA: (6) 6V, 9 Ah internal batteries

Voltage

500 VA: 12 Vdc

 

750–1000 VA: 24 Vdc

 

1500 VA: 36 Vdc

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at

 

nominal line and no supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Run Times

5 minutes, typical at full load

 

 

￿￿￿￿Battery times are approximate and may vary depending on the load configuration and battery charge.

Powerware® 5115 Rack-Mount User’s Guide : 164201449 Rev A www.powerware.com

45