UPS Maintenance

Replacing Batteries

NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

With the hot-swappable battery feature, UPS batteries can be replaced easily without turning the UPS off or disconnecting the load.

If you prefer to remove input power to change the battery: 1) Press and hold the Off button until the long beep ceases (approximately five seconds), then unplug the UPS; 2) Wait 60 seconds while the internal processor shuts down before you disconnect the battery.

Consider all warnings, cautions, and notes before replacing batteries.

W A R N I N G

SBatteries can present a risk of electrical shock or burn from high short-circuit current. The following precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries.

SELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury.

How to Replace Extended Battery Modules

Use the following procedure to replace EBMs:

1.Unplug the EBM cable from the UPS.

2.Replace the EBM. See “Recycling the Used Battery” on page 38 for proper disposal.

3.Plug the new EBM into the UPS as shown in Figure 19.

4.For additional EBMs, plug the EBM cable of the second cabinet into the battery connector on the first EBM.

UPS Battery

 

Connector

EBM

 

Battery

 

 

 

 

Connector

 

 

EBM

 

 

Cable

 

Figure 19. EBM Connections (120V Model Shown)