Specifications

Table 6. Environmental and Safety

 

Low Voltage Models

High Voltage Models

 

 

Operating Temperature

10°C to 40°C (50°F to 104°F)

 

Optimal battery performance: 25°C (77°F)

Storage Temperature

0°C to 25°C (32°F to 77°F)

Transit Temperature

-25°C to 55°C (-13°F to 131°F)

Relative Humidity

5–95% noncondensing

Operating Altitude

Up to 3,000 meters above sea level

Transit Altitude

Up to 15,000 meters above sea level

Audible Noise

Less than 40 dBA Normal mode, typical load

 

Less than 55 dBA Battery mode

Surge Suppression

ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-5

Safety Conformance

UL 1778, UL 497A;

UL 1778, UL 497A (data line only);

 

CAN/CSA C22.2, No. 107.1;

CAN/CSA C22.2, No. 107.1;

 

NOM-019-SCFI

EN 50091-1-1 and IEC 60950

Agency Markings

UL, cUL, NOM

UL and cUL; CE, C-Tick, LGA/GS, DEMKO

EMC

FCC Part 15, ICES-003, VCCI

EN 50091-2, FCC Part 15, ICES-003

 

 

 

Table 7. Battery

Configuration

1000 VA:

(2)

24V, 9 Ah internal batteries

 

1500 VA:

(4)

48V, 7 Ah internal batteries

 

2200 VA:

(4)

48V, 12 Ah internal batteries

EBM Configuration

PW5125 EBM-24: (8) 24V, 9 Ah batteries

 

PW5125 EBM-48: (8) 48V, 9 Ah batteries

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full

 

load discharge

 

External battery: recharging at 80% load or less is recommended; no more than 16x discharge

 

time to 90% usable capacity at nominal line voltage after full load discharge; an external

 

battery charger is recommended for faster recharge times when using more than 2 EBMs.

Monitoring

Advanced monitoring for earlier failure detection and warning; auto detection of additional

 

EBMs

 

 

 

 

 

 

Powerware® 5125 Tower (1000–2200 VA) User’s Guide S Rev B www.powerware.com

41