Specifications
Table 6. Environmental and Safety
| Low Voltage Models | High Voltage Models |
|
| |
Operating Temperature | 10°C to 40°C (50°F to 104°F) | |
| Optimal battery performance: 25°C (77°F) | |
Storage Temperature | 0°C to 25°C (32°F to 77°F) | |
Transit Temperature | ||
Relative Humidity | ||
Operating Altitude | Up to 3,000 meters above sea level | |
Transit Altitude | Up to 15,000 meters above sea level | |
Audible Noise | Less than 40 dBA Normal mode, typical load | |
| Less than 55 dBA Battery mode | |
Surge Suppression | ANSI C62.41 Category B (formerly IEEE 587), IEC | |
Safety Conformance | UL 1778, UL 497A; | UL 1778, UL 497A (data line only); |
| CAN/CSA C22.2, No. 107.1; | CAN/CSA C22.2, No. 107.1; |
| EN | |
Agency Markings | UL, cUL, NOM | UL and cUL; CE, |
EMC | FCC Part 15, | EN |
|
|
|
Table 7. Battery
Configuration | 1000 VA: | (2) | 24V, 9 Ah internal batteries |
| 1500 VA: | (4) | 48V, 7 Ah internal batteries |
| 2200 VA: | (4) | 48V, 12 Ah internal batteries |
EBM Configuration | PW5125 | ||
| PW5125 | ||
Type | Sealed, | ||
Charging | Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full | ||
| load discharge | ||
| External battery: recharging at 80% load or less is recommended; no more than 16x discharge | ||
| time to 90% usable capacity at nominal line voltage after full load discharge; an external | ||
| battery charger is recommended for faster recharge times when using more than 2 EBMs. | ||
Monitoring | Advanced monitoring for earlier failure detection and warning; auto detection of additional | ||
| EBMs |
|
|
|
|
|
|
Powerware® 5125 Tower | 41 |