Troubleshooting

Silencing an Audible Alarm

To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. The alarm does not silence if there is a low battery condition.

Table 9. Troubleshooting Guide

Alarm or Condition

Possible Cause

Action

 

 

 

 

 

The µindicator is not

The power cord is not

Check the power cord connections.

on; the UPS does not start.

connected correctly.

 

 

 

 

 

 

The wall outlet is faulty.

Have a qualified electrician test and repair the outlet.

The µindicator is flashing; power is not available at the UPS output receptacles.

The UPS is in Standby mode.

Press the On button to supply power to the connected equipment.

The UPS does not provide the

The batteries need charging

Plug the UPS into a power outlet for 24 hours to charge

expected backup time.

or service.

the battery. After charging the battery, press and hold

 

 

the

button for 3 seconds; then check the

 

 

indicator.

 

 

 

If the

indicator is still on, see “UPS Maintenance”

 

 

on page 33 to replace the battery.

 

The self-test failed.

Plug the UPS into a power outlet for at least 3 hours to

 

 

charge the battery. After charging the battery, press

 

 

and hold the

button for 3 seconds; then check the

 

 

indicator.

 

 

If the

indicator is still on, shut down the UPS and

 

 

contact your service representative.

 

 

 

 

UPS internal temperature is

The UPS shuts down automatically in 10 seconds. Turn

 

too high.

off and unplug the UPS. Clear vents and remove any

 

 

heat sources. Ensure the airflow around the UPS is not

 

 

restricted. Wait at least 5 minutes and restart the

 

 

UPS. If the condition persists, contact your service

 

 

representative.

 

 

 

1 beep every 4 seconds.

UPS on battery.

The UPS is powering the equipment with battery

 

 

power. Prepare your equipment for shutdown.

 

 

 

 

2 beeps every 2 seconds.

The battery is running low.

3 minutes or less of battery power remains (depending

 

on load configuration and battery charge).

 

Save your work and turn off your equipment. The

 

alarm cannot be silenced.