Quadra-Fire owner manual A. Horizontal Termination, DV400S DIRECT VENT ROOM HEATER

Models: DV400S

1 32
Download 32 pages 16.84 Kb
Page 10
Image 10
A. Horizontal Termination

R

DV400S DIRECT VENT ROOM HEATER

A. Horizontal Termination

Refer to Chart A and Figure 2 for horizontal venting recommendations. The minimum vertical rise allowed for horizontal termination is 2" from the top of the heater. The maximum horizontal run allowed for venting is 15' with a minimum 4' rise.

A single vertical to horizontal elbow is already calculated into the allowable 15' run. Each additional elbow reduces the maximum horizontal distance by 3' feet.

Example: When using three elbows, the maximum horizontal distance has been reduced to 9' (3 - 1 = 2 elbows x 3' = 6'; 15' max. - 6' of elbows = 9' of horizontal run.) Even with only these three elbows ( the equivalent of 6' additional horizontal feet) you now need a minimum of 4' of vertical rise. See Chart A.

If a vertical - to - horizontal elbow is enclosed within a wall, floor or ceiling, an air space clearance of 3" must be maintained.

Due to the many different combinations that can be used when constructing venting, the number of vent sections required can only be determined by the installer.

Horizontal venting must terminate within the shaded area shown in Fig. 2. Chart A illustrates the figures included in that shaded area. For example, if your vertical rise is the minimum two feet, venting can terminate anywhere between 20 - 1/2"

(includes wall thickness and assumes 4", and venting required to termination cap) and 10' feet.

Venting termination must not be recessed into the wall or siding. Fig 3 on Page 9 illustrates termination cap location and minimum dimensions for each termination application. Or follow ANSI Z223.1, latest edition.

Note: Horizontal runs will require the use of one vent support for every 3' of vent.

V

 

 

 

 

 

 

15' MAX. HORIZONTAL RUN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2'

 

3'

 

4'

 

5'

 

6'

 

7'

 

8'

 

9'

 

10'

 

11'

 

12'

 

13'

 

14'

 

15'

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16'

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

T

 

 

 

 

 

 

 

 

 

 

 

 

 

CI

Thru

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

A

 

4'

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

L

 

 

 

 

 

 

 

 

 

 

 

 

 

3'

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

I

2'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHART A - Venting Combinations

Note: A horizontal run of vent must have a 1/4" rise for every 1 ft. of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and the possibility of a fire.

 

VENTING CAN ONLY TERMINATE

 

WITHIN THIS AREA.

 

 

15' MAX.

 

 

 

16'

 

 

MAX.

 

 

4'

2'

 

 

MIN.

 

 

29"

591/2"*

* MINIMUM VENT

 

 

 

15" MIN.

HEIGHT (CENTER)

 

(SEE NOTE)

 

 

 

10' MAX.

 

Fig. 2 - Horizontal Lenth

March 4, 2002

Page 10

30211C

Page 10
Image 10
Quadra-Fire owner manual A. Horizontal Termination, DV400S DIRECT VENT ROOM HEATER, CHART A - Venting Combinations