Quadra-Fire DV400S Horizontal Termination Requirements, V = vent terminal, A = air supply inlet

Models: DV400S

1 32
Download 32 pages 16.84 Kb
Page 11
Image 11
Fig. 3 - HORIZONTAL TERMINATION REQUIREMENTS

R

DV400S DIRECT VENT ROOM HEATER

Fig. 3 - HORIZONTAL TERMINATION REQUIREMENTS

A.*12” (30cm) minimum: Clearance above grade, veranda, porch, deck, or balcony.

B.*12” (30cm) minimum: Clearance to window or door that may be opened.

C.12” (30cm) minimum: Clearance to permanently closed window (recommended to prevent condensation on window) or window that may be opened.

D.18” (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2’ (60cm) from the centerline of the terminal.

E.12” (30cm) minimum: Clearance to unventilated soffit.

F.Clearance to outside corner. Clearance in accordance with local installation codes and the requirements of the

gas supplier.

G.Clearance to inside corner. Clearance in accordance with local installation codes and the requirements of the gas supplier.

H.*Not to be installed above a meter/regulator (gas or electrical) assembly within 3’ (90cm) horizontally from the centerline of the meter/regulator.

I.3’ (91cm) USA/6' (183cm)Canada minimum: Clearance to service regulator vent outlet.

J.12" (30cm) minimum: Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance.

K.3’ (91cm) USA/6' (183cm)Canada minimum: Clearance to a mechanical air supply air inlet.

L.*+7’ (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on public property.

M.*#12” (30 cm) minimum: Clearance under veranda, porch, deck, or balcony.

N.Clearance to adjacent building or deck. Clearance in accordance with local installation codes and the requirements of the gas supplier.

+A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single-family dwellings and serves both dwellings.*

# Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*

*As specified in CGA B149 Installation Codes

Note: Local Codes or regulations may require different clearances.

D

 

 

 

 

 

 

 

N

E

 

 

 

 

 

 

 

 

 

V

 

 

 

 

B

 

 

 

 

 

L

 

Fixed

H

 

 

 

V

Openable

 

 

 

 

Closed

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

F

 

C

I

M

 

G

 

 

K

 

 

A

V

 

A

 

V

 

 

 

J

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

V = vent terminal

A = air supply inlet

= area where terminal is not permitted

March 4, 2002

Page 11

30211C

Page 11
Image 11
Quadra-Fire DV400S owner manual Horizontal Termination Requirements, V = vent terminal, A = air supply inlet