Quadra-Fire DV400S owner manual VentChimney Height, Figure Adaptation to Masonry Chimney

Models: DV400S

1 32
Download 32 pages 16.84 Kb
Page 16
Image 16
Figure 10 -Vent (Chimney) Height

R

DV400S DIRECT VENT ROOM HEATER

LISTED

HORIZONTAL OVERHANG

VERTICAL WALL

2 Ft. Min.

EXHAUST

INTAKE AIR Figure 11

2Ft.

Min.

CAP

LOWEST

DISCHARGE

OPENING

X

12

ROOF PITCH IS X/12

H (MIN.)-MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

WALL THIMBLE/

TRIM COLLAR

SEAL WITH SILICONE

SEAL WITH SILICONE

24" MINIMUM VERTICAL HEIGHT DURA-VENT GS C. Existing Masonry Chimney Installation VENTING

6"

4'' UL 1777 LISTED GAS VENT INNER FLEX LINER

INSIDE CHIMNEY DIAMETER

6" MINIMUM

Roof Pitch

H (min.) ft.

flat to 6/12

1.0

6/12 to 7/12

1.25

over 7/12 to 8/12

1.5

over 8/12 to 9/12

2.0

over 9/12 to 10/12

2.5

over 10/12 to 11/12

3.25

over 11/12 to 12/12

4.0

over 12/12 to 14/12

5.0

over 14/12 to 16/12

6.0

over 16/12 to 18/12

7.0

over 18/12 to 20/12

7.5

over 20/12 to 21/12

8.0

 

 

Figure 10 -Vent (Chimney) Height

WARNING

WHEN VENT SECTIONS EXCEEDING 3 FEET IN LENGTH ARE INSTALLED BETWEEN AN OFFSET/RETURN, STRUCTURAL SUPPORT MUST BE PROVIDEDTO REDUCE OFF-CENTER LOADING AND PREVENT VENT SECTIONS FROM SEPARATING AT THE VENT JOINTS.

Figure 11

Adaptation to Masonry Chimney

C. Existing Masonry Chimney Installation

This installation is subject to local jurisdic- tion. Some codes may require the use of another liner for intake air. If so, the 4” aluminum liner should be inside a 6” UL 181 listed liner.

This Heater can be vented through an existing Masonry Chimney but the chimney must be lined with one UL 1777 listed 4” aluminum flexible gas vent liner for exhaust. The existing Flue will be used to supply the air intake to the galvanized steel Flue system. See Figure 11.

March 4, 2002

Page 16