Pressure

Step 6. The Gas Supply Line

NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).

NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air.

NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13 mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch (13 mm) gas supply line.

GAS LINE Natural Gas ACCESS

USE A WRENCH ON

SHUT-OFF VALVE

WHEN TIGHTENING

GAS LINE.

MANUAL

SHUT-OFF

VALVE

FLEX CONNECTOR

GAS VALVE Propane

CONTROL VALVE

To install the gas supply line:

A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substi- tuting for these components, please consult local codes for compliance.

Locate the gas line access hole in the outer casing of the fireplace.

The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox.

Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve.

When attaching the pipe, support the control so that the lines are not bent or torn.

After the gas line installation is complete, all connec- tions must be tightened and checked for leaks with a commercially-available, non-corrosive leak check solu- tion. Be sure to rinse off all leak check solution following testing.

!WARNING: DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.

Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.

At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration.

Figure 33. Gas Supply Line

Step 7. Gas Pressure Requirements

Pressure requirements for Quadra-Fire gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

 

 

 

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa).

30

Quadra-FireQV-PIER, QV-ST Series: HV-IPI2005-901 Rev. G • 2/06

Page 30
Image 30
Quadra-Fire QV-PIER, QV-ST owner manual Pressure, Natural Gas, Propane, inches