Quadra-Fire CASTILEI-CE-MBK, SANTAFEI-CE-MBK Castile & Santa Fe CE Insert D. Floor Protection

Models: CASTILEI-CE-MBK SANTAFEI-CE-MBK

1 36
Download 36 pages 9.8 Kb
Page 21
Image 21
Castile & Santa Fe CE Insert

R

B.Masonry and Factory-Built Fireplaces * (Shown on a CASTILE INSERT)

Maximum Mantel Depth: 12 inches (305mm)

 

Face

Mantel

 

Trim

 

 

B

C

 

 

 

 

 

 

 

Side Wall

 

 

 

 

 

 

A

 

 

D

 

 

F

 

E

 

 

Figure 22.1

 

 

 

 

 

 

 

 

Inches

Millimeters

A

Insert side to combustible side wall

16

406

B

Insert top to mantel

 

 

12

305

C

Insert top to maximum. 2-1/4 inch

4-3/4

121

 

(57mm) face trim

 

 

 

 

D

Insert side to maximum. 2-1/4 inch

10

254

 

(57mm) face trim

 

 

 

 

*the Castile and Santa Fe inserts are only intended for installation into a masonry or factory built fire- place

C. Minimum Opening for Masonry and Factory-Built Fireplaces

B

C

A

 

 

D

Figure 22.2

 

Location

Millimeters (Castile/Santa Fe)

A

Rear Width

600/ 610

B

Depth

432/ 406

C

Height

540/ 591

D

Front Width

714/ 743

Castile & Santa Fe CE Insert

D. Floor Protection

 

 

Inches

Millimeters

E

Floor protection hearth extension from

6

152

 

door opening

 

 

 

F

Floor protection to the side of door

6

152

 

opening

 

 

E. Prefabricated Metal Chimney

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements:

•Must be minimum 152mm inside diameter of high temperature chimney listed to UL 103 HT (2100oF).

•Must use components required by the manufacturer for installation.

•Must maintain clearances required by the manufacturer for installation.

•Refer to manufacturers instructions for installation

•This insert is listed to UL 1482 Standard and is approved for installation into listed factory-built zero clearance fire- places listed to UL 127 conforming to the following speci- fications and instructions:

•The original factory-built clearance fireplace chimney cap must be re-installed after installing the approved chimney liner meeting type UL 103 HT requirements (2100°F) per UL 1777.

•If the chimney is not listed as meeting HT requirements, or if the factory built fireplace was tested prior to 1998, a full height listed chimney liner must be installed from the appliance flue collar to the chimney top.

•The liner must be securely attached to the insert flue collar and the chimney top.

•The air flow of the factory-built zero-clearance fireplace system must not be altered. The flue liner top support attachment must not reduce the air flow for the existing air-cooled chimney system.

•No dilution air is allowed to enter the chimney.

1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.t

2.Seal damper area of chimney around chimney connector with a high temperature sealant or seal insert against the face of the fireplace.

3.Both methods must be removable and replaceable for cleaning and re-installation.