Raypak 0180B Type H manual Mounting, Vent Damper Operation

Models: 0180B Type H

1 40
Download 40 pages 26.78 Kb
Page 12
Image 12
Mounting

Mounting

On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.

The vent damper is set up for a continuous pilot sys- tem. If the vent damper is installed on a system with an Intermittent Pilot or Hot Surface Ignition, the energy savings of the vent damper can be improved by plug- ging the hole in the vent damper blade using the knockout plug provided in the parts envelope.

Hole in Vent Damper Blade

Closed Position

DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a haz- ardous condition.

Fig. 8: Vent Damper

Fig. 9: Installing The Vent Damper in Horizontal

& Vertical Vents

Fig. 10: D80D General Wiring Diagram

Install the vent damper to service only the single appliance for which it is intended. If improperly installed, a hazardous condition, such as an explo- sion or carbon monoxide poisoning, could result.

Vent Damper Operation

For safe, efficient operation, the vent damper and all flue-product-carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources.

Check vent damper operation as follows:

1.When the boiler is off, check that the vent damper position indicator points to the closed position (see Fig. 11).

Damper Position Indicator

Damper Open

Damper Closed

Fig. 11: Vent Damper Position Indicator

12

Page 12
Image 12
Raypak 0180B Type H manual Mounting, Vent Damper Operation