Raypak 0180B Type H manual 10Defective ignition module or defective gas valve

Models: 0180B Type H

1 40
Download 40 pages 26.78 Kb
Page 35
Image 35
10)Defective ignition module or defective gas valve.

10)Defective ignition module or defective gas valve.

10)Before module goes into a lock-out, check voltage across MV and MV/ PV. If no 24V is present, replace module. If 24V is present, replace gas valve.

3)Pilot Outage.

1) Too low or too high gas pressures.

1)

Adjust inlet gas pressure as shown

(Standing pilot models)

 

 

 

on rating plate.

 

2)

Restricted pilot.

2)

Clean pilot orifice.

 

3)

Weak thermocouple.

3)

Replace thermocouple.

 

 

 

4)Yellow lazy flame.

1) Too low gas pressure.

1) Adjust manifold pressure as shown

 

 

 

 

on rating plate.

 

2)

Restricted burner intake ports.

2)

Clean burners free of debris or in-

 

 

 

 

sects.

 

3)

Restricted gas line.

3)

Clean gas line or increase gas line

 

 

 

 

piping.

 

 

 

5)Sooting

1) Insufficient combustion air.

1) Refer to installation instructions re-

 

 

 

 

garding combustion air require-

 

 

 

 

ments.

 

2)

Improper venting.

2)

Refer to installations instructions.

 

3)

Severe yellow burner flames.

3)

See yellow flame section above.

 

 

 

 

 

 

 

 

 

 

35

Page 35
Image 35
Raypak 0180B Type H manual 10Defective ignition module or defective gas valve