Location of the openings is the same as in the previ- ous case - that is, within 12" of the top, and within 12" of the bottom of the enclosure. If horizontal ducts are used, the area must be doubled and the duct area shall not be less than the area of the openings they connect, and in no case shall the smallest dimension be less than 3".

Venting Connections

These boilers have built-in drafthoods. Vent piping the same size or larger than the drafthood outlet is recom- mended; however, when the total vent height (drafthood outlet to vent terminal) is at least ten (10) feet, the vent pipe size may be reduced by one size only as specified in the latest edition of the National Fuel Gas Code, ANSI Z223.1.

As much as possible, avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Maximum vent connector horizontal length shall be 1-1/2 feet (18 inches) for each inch of connector diameter as shown in Table E.

 

Vent

Max.

Model No.

Connector

Horizontal

 

Diameter (in.)

Length (ft)

 

 

 

0042

4

6

 

 

 

0066, 0090

5

7.5

 

 

 

0135

6

9

 

 

 

0180

7

10.5

 

 

 

Table E: Maximum Horizontal Length of Vent Pipe

Gas vents supported only by the flashing and extend- ing above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads. We recommend use of insulated vent pipe spacer through the roofs and walls.

For protection against rain or blockage by snow, the vent pipe must terminate with a listed vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1.

The discharge opening must be a minimum of two (2) feet vertically from the roof surface and at least two (2) feet higher than any part of the building within ten (10) feet. Vent stack shall be at least five (5) feet in vertical height above the drafthood outlet.

The vent cap location shall have a minimum clearance of four (4) feet horizontally from, and in no case above or below, unless a 4-foot horizontal distance is main- tained, from electric meters, gas meters, regulators and relief equipment.

The weight of the vent stack or chimney must not rest on the boiler's drafthood. Support must be provided in compliance with applicable codes. The boiler top and drafthood must be readily removable for maintenance and inspection. Vent pipe should be adequately sup- ported to maintain proper clearances from combustible construction.

Type "B" double-wall (or equivalent) vent pipe is rec- ommended. However, single-wall metal vent pipe may be used as specified in the latest edition of the National Flue Gas Code ANSI Z223.1.

Lowest Discharge

Opening

Listed Cap

Listed Gas Vent

X

12

Roof Pitch is X/12

H - Minimum Height from

Roof to Lowest

Discharge Opening

Refer to Table F for detailed information

Fig. 4: Minimum Height from Roof to Lowest Discharge

Opening

9

Page 9
Image 9
Raypak 0180B Type H manual Venting Connections, Vent Max Model No Connector Horizontal Diameter Length ft

0180B Type H specifications

The Raypak 0180B Type H is a standout model in the realm of heating solutions, offering a unique blend of efficiency and reliability for both residential and commercial applications. Known for its robust design and advanced technologies, the 0180B Type H is specifically engineered to provide exceptional performance while ensuring energy savings.

One of the key features of the Raypak 0180B Type H is its compact design, which makes it ideal for installation in tight spaces without sacrificing performance. The unit incorporates a patented heat exchanger that enhances thermal efficiency, ensuring that a higher percentage of energy is converted into usable heat. This design not only maximizes performance but also minimizes waste, contributing to lower operating costs and reduced environmental impact.

Equipped with Raypak's state-of-the-art digital control system, the 0180B Type H provides precise temperature regulation and monitoring. Users can easily set desired temperature parameters, while the system automatically adjusts to maintain optimal heating levels. This technology not only enhances user convenience but also ensures that the system operates at peak efficiency, further extending the lifespan of the unit.

The 0180B Type H features a durable construction that includes corrosion-resistant materials, ensuring longevity even in challenging environments. Its design is tailored to withstand extreme weather conditions, making it a reliable choice for various applications, including pool heating, spa heating, and process heating. Additionally, the unit is equipped with advanced safety features, such as built-in pressure relief valves and automatic shut-off mechanisms, providing peace of mind for users.

Another notable characteristic of the Raypak 0180B Type H is its compatibility with alternative energy sources. The unit can be easily integrated with solar heating systems, enhancing energy efficiency and sustainability. This flexibility makes it an attractive option for eco-conscious consumers looking to reduce their carbon footprint.

In summary, the Raypak 0180B Type H combines advanced technology with a user-friendly interface, robust construction, and energy-efficient design. Its unique features cater to a variety of heating needs, establishing it as a premier choice for individuals and businesses alike. Whether for residential or commercial use, the 0180B Type H is designed to deliver consistent, reliable heating solutions that stand the test of time.