8.Locate and guard vent termination to prevent acci- dental contact by people or pets.

9.DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area.

10.DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze, causing ice formations.

11.Locate or guard vent to prevent condensate from damaging exterior finishes. Use a rust-resistant sheet metal backing plate against brick or mason- ry surfaces.

12.DO NOT extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.

U.S. Installations

Refer to the latest edition of the National Fuel Gas Code.

Vent termination requirements are as follows:

1.Vent must terminate at least 4 ft below, 4 ft hori- zontally from or 1 ft above any door, window or gravity air inlet to the building.

2.The vent must not be less than 7 ft above grade when located adjacent to public walkways.

3.Terminate vent at least 3 ft above any forced air inlet located within 10 ft.

4.Vent must terminate at least 4 ft horizontally, and in no case above or below unless 4 ft horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.

5.Terminate vent at least 6 ft away from adjacent walls.

6.DO NOT terminate vent closer than 5 ft below roof overhang.

7.The vent terminal requires a 12 in. vent terminal clearance from the wall.

8.Terminate vent at least 1 ft above grade, including normal snow line.

9.Multiple direct vent installations require a 4 ft clearance between the ends of vent caps located on the same horizontal plane.

Canadian Installations

Refer to latest edition of B149.1.

A vent shall not terminate:

1.Directly above a paved sidewalk or driveway which is located between two single-family dwell- ings and serves both dwellings.

2.Less than 7 ft (2.13 m) above a paved sidewalk or paved driveway located on public property.

3.Within 6 ft (1.8 m) of a mechanical air supply inlet to any building.

4.Above a meter/regulator assembly within 3 ft (915

mm)horizontally of the vertical centre-line of the regulator.

5.Within 6 ft (1.8 m) of any gas service regulator vent outlet.

6.Less than 1 ft (305 mm) above grade level.

7.Within the 3 ft (915 mm) of a window or door which can be opened in any building, any non-mechani- cal air supply inlet to any building or the combus- tion air inlet of any other appliance.

8.Underneath a verandah, porch or deck, unless the verandah, porch or deck is fully open on a mini- mum of two sides beneath the floor, and the dis- tance between the top of the vent termination and the underside of the verandah, porch or deck is greater than 1 ft (305 mm).

Changing the Flue Outlet

Follow these instructions to change the flue connec- tion from the standard top location to the rear of the heater.

1.Disconnect all electrical power from the heater (if applicable).

2.Disconnect or isolate the main gas pipe from the heater (if applicable).

3.Remove the screws, gasket and dustcover from the rear of the heater.

4.Remove the screws, stainless steel flue cover and gasket from the branch side of the tee located in the flue box at the rear of the heater.

27

Page 27
Image 27
Raypak 302A-902A manual Changing the Flue Outlet, Canadian Installations

302A-902A specifications

The Raypak 302A-902A is a highly regarded pool and spa heater, known for its efficiency and reliability in delivering warmth to residential and commercial aquatic applications. This heater stands out due to its robust design, advanced technology, and user-friendly features.

One of the key characteristics of the Raypak 302A-902A is its dual fuel capability, which means it can run on either natural gas or propane. This flexibility allows users to choose their preferred fuel type, contributing to operational efficiency and cost-effectiveness. With a BTU output ranging from 302,000 to 902,000, the Raypak heater is capable of quickly heating large volumes of water, making it ideal for pools, spas, and hot tubs.

The heater incorporates advanced technology such as a stainless steel heat exchanger, which not only ensures excellent thermal conductivity but also promotes durability against corrosion. This is especially advantageous in harsh environments, where exposure to chemicals can significantly impact the lifespan of traditional copper heat exchangers. The Raypak 302A-902A's heat exchanger is designed to withstand the rigors of constant use while maintaining high performance levels.

Another prominent feature of the Raypak 302A-902A is its digital display control system, which simplifies the operation and monitoring of the heater. Users can easily set and adjust temperatures, as well as access diagnostic information, all through an intuitive interface. This digital control not only enhances user experience but also aids in the timely maintenance of the unit.

Energy efficiency is another major selling point of the Raypak 302A-902A. The heater is designed with environmentally friendly practices in mind, utilizing a low NOx burner that minimizes harmful emissions. This not only meets environmental regulations but also makes it a greener alternative for heating needs.

In terms of installation, the compact design of the Raypak 302A-902A allows for versatile placement options, whether in a residential backyard or a commercial environment. Its user-friendly installation process ensures that homeowners and businesses alike can enjoy the benefits of heated water with minimal hassle.

Overall, the Raypak 302A-902A is an exemplary choice for anyone seeking a high-quality, efficient, and flexible pool and spa heating solution. Its combination of robust engineering, advanced technology, and user-focused features solidifies its position as a leader in the market, promising effective heating for years to come. Whether for personal enjoyment or commercial use, this heater delivers exceptional performance that meets diverse heating needs.