External Lights

External Lights

Light

Color

Indication

 

 

 

Power

Blue

Main power is on

 

 

 

Call For Heat

Yellow

Thermostat is closed

 

 

 

Safety

Red

One or more safeties is inopera-

tive

 

 

 

 

 

Ignition

Red

Ignition module is inoperative

 

 

 

Flow

Green

Flow is present

 

 

 

Blower 1

Green

Blower 1 is on

 

 

 

Stage 1

Green

Stage 1 is on

 

 

 

Stage 2

Green

Stage 2 is on

 

 

 

Internal Lights

Light

Color

Indication

 

 

 

Board Power

Yellow

Board power is on

 

 

 

Low Water Cut-Off

Red

Low water cut-off is open

 

 

 

Blocked Vent

Red

Vent is blocked

 

 

 

Manual Reset Hi-Limit

Red

Manual reset is open

 

 

 

Low Gas Pressure

Red

Low gas pressure

Switch

 

 

 

 

 

High Gas Pressure

Red

High gas pressure

Switch

 

 

 

 

 

(Not Used)

Red

 

 

 

 

PVC Vent Limit

Red

Vent temperature exceeds

limits

 

 

 

 

 

Auto Reset High Limit

Red

Auto reset option

 

 

 

Table N: LED Indicators

24.Upon sufficient flow from the heater pump, the flow switch contacts will close.

25.The flow light is energized; located on the diag- nostics panel.

26.A 24 VAC signal is also sent to the “TH” terminal located on the ignition module.

27.Once the 24 VAC “TH” signal is received at the ignition module, a 120 VAC signal is sent from F2 on the ignition module to the 120 VAC pilot duty terminals, located at J-14 on the circuit board.

28.The 120 VAC signal continues to the coil of the blower relay K-3 (N.O.).

29.The 120 VAC signal continues to the 120 VAC safety terminals located at J-13 on the circuit board.

30.When the coil on relay K-3 (N.O.) is powered, the relay contacts (K-3) close and energizes the blow- er from the J-8 connections on the CPW board.

31.After proper air pressure is received in the air plenum, the air pressure switch will close.

32.A 24 VAC signal is now sent to the blower LED on the diagnostics board.

33.Power is applied to the optional equipment inter- lock connection (normally jumpered).

34.The 24 VAC signal is then sent to the 24 VAC safe- ty connector.

35.24 VAC is now sent to the pressure switch (P.S.) terminal on the ignition module.