10.To restart system, follow lighting instructions in the Operation section.

11.Check to see that the high limit control is set above the design temperature requirements of the system.

For multiple zones: Check to make sure the flow is adjusted as required in each zone.

12.Check that the heater is cycled with the thermo- stat. Raise to the highest setting and verify that the heater goes through the normal start-up cycle. Re- duce to the lowest setting and verify that the heater goes off.

13.Observe several operating cycles for proper oper- ation.

14.Set the room thermostat or tankstat to desired temperature.

15.Review all instructions shipped with this heater with owner or maintenance person, return to enve- lope and give to owner or place the instructions in- side front panel on heater.

OPERATION

Lighting Instructions

1.Before lighting, make sure you have read all of the safety information in this manual.

2.Set the thermostat to the lowest setting.

3.Turn off all electrical power to the appliance.

4.This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

5.Remove upper front panel.

6.Turn on main manual gas valve.

7.Wait 5 minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas, STOP! Follow the steps in the safety informa- tion on the front cover of this manual. If you do not smell gas, go to next step.

8.Turn on all electrical power to the appliance.

9.Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre- purge time delay (15 seconds). After igniter reach- es temperature (45 seconds) the main valve will open. System will try for ignition three times. If flame is not sensed, lockout will commence.

10.If the appliance will not operate, follow the instruc- tions “To Turn Off Gas To Appliance,” and call your service technician or gas supplier.

11.Replace access panel.

12.If heater fails to start, verify the following:

a.There are no loose connections or that the service switch is off.

b.High temperature limit switch is set above wa- ter temperature.

c.Thermostat is set above room temperature.

d.Gas is on at the meter and the heater.

e.Incoming gas pressure to the gas valve is NOT less than 5.0 in. WC for natural gas, 11.0 in. WC for propane gas.

To Turn Off Gas To Appliance

1.Set the thermostat to lowest setting.

2.Turn off all electrical power to the appliance if serv- ice is to be performed.

3.Remove upper front panels.

4.Turn off main manual gas valve.

5.Replace access panel.

49

Page 49
Image 49
Raypak 302A-902A manual Operation, Lighting Instructions, To Turn Off Gas To Appliance

302A-902A specifications

The Raypak 302A-902A is a highly regarded pool and spa heater, known for its efficiency and reliability in delivering warmth to residential and commercial aquatic applications. This heater stands out due to its robust design, advanced technology, and user-friendly features.

One of the key characteristics of the Raypak 302A-902A is its dual fuel capability, which means it can run on either natural gas or propane. This flexibility allows users to choose their preferred fuel type, contributing to operational efficiency and cost-effectiveness. With a BTU output ranging from 302,000 to 902,000, the Raypak heater is capable of quickly heating large volumes of water, making it ideal for pools, spas, and hot tubs.

The heater incorporates advanced technology such as a stainless steel heat exchanger, which not only ensures excellent thermal conductivity but also promotes durability against corrosion. This is especially advantageous in harsh environments, where exposure to chemicals can significantly impact the lifespan of traditional copper heat exchangers. The Raypak 302A-902A's heat exchanger is designed to withstand the rigors of constant use while maintaining high performance levels.

Another prominent feature of the Raypak 302A-902A is its digital display control system, which simplifies the operation and monitoring of the heater. Users can easily set and adjust temperatures, as well as access diagnostic information, all through an intuitive interface. This digital control not only enhances user experience but also aids in the timely maintenance of the unit.

Energy efficiency is another major selling point of the Raypak 302A-902A. The heater is designed with environmentally friendly practices in mind, utilizing a low NOx burner that minimizes harmful emissions. This not only meets environmental regulations but also makes it a greener alternative for heating needs.

In terms of installation, the compact design of the Raypak 302A-902A allows for versatile placement options, whether in a residential backyard or a commercial environment. Its user-friendly installation process ensures that homeowners and businesses alike can enjoy the benefits of heated water with minimal hassle.

Overall, the Raypak 302A-902A is an exemplary choice for anyone seeking a high-quality, efficient, and flexible pool and spa heating solution. Its combination of robust engineering, advanced technology, and user-focused features solidifies its position as a leader in the market, promising effective heating for years to come. Whether for personal enjoyment or commercial use, this heater delivers exceptional performance that meets diverse heating needs.