Fig. 27: Horizontal
Condensing Heat Exchanger (Category IV)
| Venting | Certified Venting | Vent Size | Maximum Vent | Combustion Air | Air Inlet | Max. Air | |
Model | Intake Pipe | Size | Intake Length | |||||
Category | Material | (inches) | Length (feet) | |||||
| Material | (inches) | (feet) | |||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
|
| UL 1738 Certified |
| 35 | Galvanized |
| 35 | |
IV | Venting Material e.g. | 8 | Subtract 10 ft per | Steel | 6 | Subtract 10 ft | ||
w/CHX | elbow, Max. 3 | PVC, ABS | per elbow, | |||||
|
|
| ||||||
|
| Steel PVC*, CPVC* |
| elbows | CPVC |
| Max. 3 elbows | |
|
|
|
|
|
|
|
| |
|
| UL 1738 Certified |
| 35 | Galvanized |
| 35 | |
IV | Venting Material e.g. | 10 | Subtract 10 ft per | Steel | 6 | Subtract 10 ft | ||
w/CHX | elbow, Max. 3 | PVC, ABS | per elbow, | |||||
|
|
| ||||||
|
| Steel PVC*, CPVC* |
| elbows | CPVC |
| Max. 3 elbows | |
|
|
|
|
|
|
|
| |
|
| UL 1738 Certified |
| 35 | Galvanized |
| 35 | |
IV | Venting Material e.g. | 12 | Subtract 10 ft per | Steel | 8** | Subtract 10 ft | ||
w/CHX | elbow, Max. 3 | PVC, ABS | per elbow, | |||||
|
|
| ||||||
|
| Steel PVC*, CPVC* |
| elbows | CPVC |
| Max. 3 elbows | |
|
|
|
|
|
|
|
|
*Contact the manufacturer for details.
**If the boiler is direct vented, a 6 to 8 in. adapter must be installed at the blower inlet.
Table Q: Horizontal
Condensing Heat Exchanger
37