Raypak 751 manual Pump Turn-offDelay, Blower Fan Pre-purge, Blower Fan Post-purge

Models: 751

1 57
Download 57 pages 31.86 Kb
Page 42
Image 42
Pump Turn-off Delay

Fig. 30: CPW Board

Pump Turn-off Delay

The CPW board has a built-in pump driver with pump turn-off delay, which allows the operator to set how long the pump will run after the boiler shuts off. The delay is factory-set for 7 minutes but can be field- adjusted from 3 minutes to 10 minutes. The pump relay can directly power a pump of up to 12.0 amps draw or 3/4 hp capacity. Pumps with larger amp draws should be energized through a pump contactor that is controlled by the CPW board.

By properly setting the pump turn-off delay, the boiler pump will continue running for a limited period of time in order to extract any residual heat from the combus- tion chamber. The pump will then shut off to conserve energy until the next call for heat.

The pump-off time delay should be set to the minimum time required to extract all residual heat from the heat exchanger. If temperature as monitored at the boiler outlet increases more than 5°F after the pump turns off following a firing cycle, the pump-off time delay should be extended by thirty seconds. Increase or decrease time delay as appropriate until outlet temperature does not spike more than 5°F after pump shut-off following a prolonged firing cycle (> 5min.)

CAUTION: The boiler requires forced water circulation when the burner is operating and the pump must be interlocked with the boiler. See the Water Piping section for minimum and maximum water flow rates and pump selection.

NOTE: Pump will come on when power is first applied to the boiler.

Blower Fan Pre-purge

The CPW board has a built-in pre-purge delay which operates the blower fan for a user-adjustable time period prior to pilot trial for ignition. The pre-purge peri- od ensures that the combustion chamber is clear of all excess combustible gases prior to commencing the pilot ignition cycle. The pre-purge delay is factory set for 45 seconds and it can be adjusted in the field from 45 seconds to 120 seconds. To optimize boiler response time on call-for-heat, set the pre-purge delay to the minimum allowed by local, state or national code.

Blower Fan Post-purge

The CPW board has a built-in post-purge delay to exhaust residual combustion products after the main gas valve closes. The post-purge timing is factory set at 3 minutes and is not field-adjustable.

Freeze Protection Feature

The CPW board is programmed to turn-off the blower in case there is a lock-out condition. If there is a call for heat signal, and the pilot valve signal is removed and not reactivated within a pre-set time for any reason, the CPW board will turn off the blower to prevent blow- ing cold air continuously and freezing the heat exchanger. The blower drives will open and the system will lock in the off state.

To restart the system, primary power or the thermostat signal must be turned off and back on. The pre-set freeze protection feature time is approximately 5 min- utes.

42

Page 42
Image 42
Raypak 751 manual Pump Turn-offDelay, Blower Fan Pre-purge, Blower Fan Post-purge, Freeze Protection Feature