of 1 million BTUH. This opening(s) shall be either located at or ducted to a point neither more than 18 inches (450 mm) nor less than 6 inches (150
mm)above the floor level. The duct can also "Goose Neck" through the roof. The duct is pre- ferred straight down 18 inches from floor, but do not place near piping. This air supply opening requirement shall be in addition to the air opening for ventilation air required in (1).
3.When air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, draft hood or similar flue gas dilu- tion device installed in the same space, in addition to the opening for ventilation air required in (1), there shall be a permanent air supply opening(s) having a total
mm)nor less than 6 inches (150 mm) above the floor level. The duct can also "Goose Neck" through the roof. The duct is preferred to be straight down 18 inches from floor, but do not place near piping.
4.Refer to the latest version of CSA B149 for addi- tional information.
WATER PIPING
General
The boiler should be located so that any water leaks will not cause damage to the adjacent area or struc- tures.
All units should be plumbed in accordance with the appropriate diagram from the following sections or per a suitable engineered piping arrangement.
CAUTION: This boiler requires forced water circulation when the burner is operating. See Table E for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the boiler to prevent boiler operation without water circulation.
Relief Valve Piping
WARNING: Pressure relief valve discharge piping must be piped near the floor close to a floor drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.
Hydrostatic Test
Unlike many other types of boilers, Raypak boilers do not require hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac-
Leaks must be repaired at once to prevent damage to the boiler. NEVER use
1.Connect fill water supply. Fill boiler with water (be sure bleed valve is open). When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, being sure to eliminate any entrapped air by using high point vents. Close feed valve. TEST AT standard oper- ating pressure for at least 24 hours.
2.Make sure constant gauge pressure has been maintained throughout test.
3.Check for leaks. Repair if found.
Low Temperature System
Boiler requires minimum inlet temperature of 105°F. Consult the following sections for piping details. (For Pool temperature requirements, See the Pool Heating Section).
Temperature & Pressure Gauge
The temperature and pressure gauge is factory- mounted in the inlet/outlet header.
12