Horizontal
These installations utilize the boiler mounted blower to draw combustion air from outdoors and vent combus- tion products to the outdoors.
UL 1738 Certified Venting Material (e.g.
For certain installations, i.e. pool,
To prevent condensate accumulation in the vent, it is required to install the horizontal portion of vent with a slight upward slope of not more than 1/4" per foot of horizontal run and an approved condensate trap must be installed per applicable codes.
WARNING: For common vent installations, contact the factory.
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
The Stainless Steel
Fig. 28: Vertical Direct Venting/Combustion Air with
Heat Exchanger (Category IV)
38