Combustion Air Filter
This heater is supplied with an integral combustion air filter. This filter will reduce the amount of particulates that pass through the combustion system and heat exchanger but will not protect against chemical inside air contamination (See Appendix). The filter must be checked periodically to verify that adequate combus- tion air is being supplied to the heater. See the Maintenance section of this manual for information on checking the filter and establishing service intervals.
Direct Vent
If outside air is drawn through the intake pipe directly to the unit for combustion:
1.Install the combustion air ducting kit.
2.Install combustion air direct vent in accordance with Fig. 23 (horizontal) or Fig. 24 (vertical) of this manual.
3.Provide adequate ventilation of the space occu- pied by the heater(s) by an opening(s) for ventilation air at the highest practical point com- municating with the outdoors. The total
4.In cold climates, and to mitigate potential freeze- up, Raypak highly recommends the installation of a motorized sealed damper on the air intake to prevent the circulation of cold air through the heater during the
TruSeal™ Combustion Air
In addition to the 4 previous steps, combustion air may be ducted directly to the heater by using PVC, CPVC or sealed
mechanical room. All ducting must be
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per- manent openings communicating directly with an additional room(s) of sufficient volume so that the com- bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determina- tion. Each opening shall have a minimum free area of 1 in.2 per 1,000 BTUH (2,225 mm2 per kW) of the total input rating of all gas utilization equipment in the con- fined space, but not less than 100 in.2 (645 cm2). One opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom of the enclosure. The mini- mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out- doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same
1.Two permanent openings, one commencing within 12 in. (305 mm) of the top, and one com- mencing within 12 in. (305 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely com- municate with the outdoors.
a.Where directly communicating with the out- doors or where communicating to the outdoors through vertical ducts, each open- ing shall have a minimum free area of 1 in.2 per 4,000 BTUH (550 mm2 per kW) of total input rating of all equipment in the enclosure.
11