Manifold Check

–0.5 in. WC from the reading recorded on the start-up checklist.

3.The desired combustion CO2 is between 8.5% and 9.0% for natural gas and 9.0% and 9.5% for propane with CO less than 150 ppm. Combustion should be checked at high and low fire (Max. and Min. fan speed) by using the service mode. Enter the service mode by pressing the UP arrow key and ENTER/MENU key simultaneously for 1 sec- ond. Set the fan speed using the UP and DOWN arrow keys.

Manifold Check

1.Check manifold gas pressure at the manifold pres- sure tap (connection “D” in Fig. 35). This pressure should read per the values in Table S for natural and propane gas.

2.If the pressure reading differs by more than ± 0.2 in. WC, STOP – Call the factory for directions on what to do next!

 

Model

 

Air Pressure

 

Setting

 

 

 

 

 

 

 

Setting (in. WC)

 

Tolerance

 

 

300

 

-0.1

 

± 0.2 in. WC

 

 

500

 

-0.2

 

± 0.2 in. WC

 

 

850

 

-0.3

 

± 0.2 in. WC

 

 

Table Q: XFyre Intake Air Pressure Settings (High Fire)

Model

High Fire

Ignition

Low Fire

300

5000

3000

1500

500

7600

3000

1750

850

5500

3000

1500

 

Table R: XFyre Fan Speed Settings

Model

Manifold Pressure (in. WC)

Natural Gas

Propane Gas

No.

High

Low

High

Low

300

-0.2

-0.1

-0.2

-0.1

500

-0.3

-0.1

-0.3

-0.1

850

-3.2

-0.2

-2.7

-0.1

NOTE: Manifold pressures should be ±0.3 in. WC.

Table S: XFyre Manifold Pressure Settings

CAUTION: Special manifold and air settings may be required.

Finishing

1.Record all data on the “Start-up Checklist” located at the back of this manual.

2.Disconnect the manometers and reconnect the cap on the air intake and reinsert or close the seal- ing screws into the bleedle valves.

3.Start-up is complete and the boiler should be oper- ating properly.

Safety Inspection

1.Check all thermostats and high limit settings.

2.During the following safety checks leave manome- ters hooked up, check and record.

3.If other gas-fired appliances in the room are on the same gas main, check all pressures on the XFyre with all other equipment running.

4.Check thermostats for ON-OFF operation.

5.Check high limits for ON-OFF operation.

6.While in operation, check flow switch operation.

7.Check the low gas pressure switch (if provided). (For proper adjustment, use the attached manometers, if available, to set pressure. The scales on the switch are approximate only.) Low gas pressure switch (if provided) must be set at 3.0 in. WC for natural gas and propane gas.

8.Make sure that the high gas pressure switch (op- tional) is set to 3.0 in. WC for both natural gas and propane gas.

Follow-Up

Safety checks must be recorded as performed. Turn boiler on. After main burner ignition:

1.Check manometer for proper readings. Specifically note the change in air intake pressure. Replace the filter if necessary. (Refer to Table Q.)

2.Cycle unit several times and re-check readings.

3.Remove all manometers and replace caps and screws.

4.Check for gas leaks one more time.

43

Page 43
Image 43
Raypak 300, 850 operating instructions Manifold Check, Finishing, Safety Inspection, Follow-Up

300, 850 specifications

Raypak is a renowned name in the heating industry, particularly known for its high-quality pool and spa heaters. Among their extensive product line, the Raypak 850, 500, 300, 400, and 700 models stand out for their reliability, efficiency, and cutting-edge technologies. Each model is designed to cater to different needs and applications while maintaining Raypak’s commitment to performance.

The Raypak 850 is designed for larger commercial pools or residential setups requiring high output. With a powerful heat exchanger made from copper and bronze, it ensures superior heat transfer and longevity. Its digital control system provides precise temperature regulation, enhancing user experience. Moreover, it features a durable construction with weather-resistant materials, ensuring lasting performance in various environments.

The Raypak 500 model offers a balance between efficiency and compactness. It features eco-friendly technology that reduces energy consumption without sacrificing performance. The integrated thermostat allows users to maintain consistent water temperatures, making it ideal for residential pools. This model is well-regarded for its user-friendly digital display, simplifying operation and monitoring.

For those needing a more moderate capacity, the Raypak 300 is an efficient choice. It combines robust engineering with an easy-to-use interface. Its advanced ignition system improves reliability while minimizing energy waste. The Raypak 300’s compact design allows for easy installation in various spaces, making it an excellent option for smaller pools.

The Raypak 400 heats water quickly and efficiently, making it suitable for both residential pools and spas. It features a high-capacity heating system that ensures optimal performance. With a clear LED display, users can easily monitor their settings, while the integrated diagnostics provide real-time feedback for maintenance and troubleshooting.

Lastly, the Raypak 700 model is known for its versatility and robust performance. It is equipped with advanced safety features, including a high limit switch and water flow detection mechanism, to ensure safe operation. The model's energy-efficient design enhances its eco-friendliness, making it a popular choice among environmentally conscious users.

Collectively, these Raypak models exemplify superior engineering, performance, and user-friendliness. Their innovative features ensure that they meet the varied demands of pool owners while providing reliable heating solutions for leisure and relaxation. Whether for commercial or residential use, the Raypak 850, 500, 300, 400, and 700 offer unmatched quality and efficiency.