Raypak 850, 300 operating instructions Preparation, Start-Up, Blower Check

Models: 300 850

1 56
Download 56 pages 35.86 Kb
Page 42
Image 42
Preparation

Preparation

WARNING: Do not turn on gas at this time.

Check Power Supply

With multi-meter at incoming power, check voltage between:

Hot - Common (≈120 VAC)

Hot - Ground (≈120 VAC) Common - Ground (< 1 VAC)

WARNING: If Common - Ground is > 1 VAC,

STOP: Contact electrician to correct ground failure. Failure to do this may burn out 120V-24V transformer, or may cause other safety control damage or failure.

Attach Manometers to Measure Pressures

1.Turn off main gas valve.

2.Attach (1) 12” scale manometer to an upstream bleedle valve on the gas supply pipe to the boiler (Measure point “A” in Fig. 35).

3.Attach (1) 12” scale manometer to the manifold pressure tap located downstream of the valve (Measure point “D” in Fig. 35).

4.Attach (1) 12” scale manometer to the tapping on the filter box. Pull black cap from air pressure switch tee and connect the manometer. NOTE: Retain caps for reinstallation later.

D

Check Gas Supply Pressure

1.Slowly turn on main gas shut-off valve.

2.Read the gas supply pressure from the manome- ter; minimum supply pressure for natural gas is 4.0 in. WC, recommended supply is 7.0 in. WC, mini- mum supply pressure for propane gas is 4.0 in. WC, recommended supply is 11.0 in. WC (dynam- ic readings, full fire input).

3.If the gas pressure is greater than 14.0 in. WC, turn off the main gas shut-off valve.

Start-Up

1.Turn power on.

2.Turn on the boiler, approximately 5 seconds after the blower starts, the igniter should start to spark (observable through the observation port located at the front, bottom of the boiler) and the gas valve will open. Look into the sight glass located at the bottom of the front panel to check igniter opera- tion.

3.The boiler ignites at 3000 RPM (as indicated on the LCD display of the user interface).

4.This boiler is equipped with a standard four-try ignition module, it will try for ignition up to four times before going into lockout. If the boiler is equipped with the optional single-try ignition mod- ule, it will try for ignition one time before going into lockout.

5.Wait until the controller indicates 100% on the fir- ing rate display screen. This will take several minutes if step modulation is enabled.

A Start-UpBlower CheckManual backgroundManual background

GASManual background

 

MODEL 300 VALVE

TO BURNER

USES SAME POINTS

A & D AS MODEL 500

 

A

B

GAS

C

D

 

 

TO BURNER

Fig. 35: Gas Pressure Measurement Locations

Blower Check

1.Check the high and low fire fan speed on the user- interface. Enter the service mode by pressing the UP arrow key and ENTER/MENU key simultane- ously for 1 second. Verify that the min. and max. fan speeds match Table R on the following page.

2.Note the high fire air intake pressure on the filter box and compare to Table Q. Excessively high pressures indicate an obstruction in the air intake or undersized/too long air intake ducting. With a clean air filter in place, record the intake air pres- sure setting on the start-up checklist. Replace the filter when the intake air pressure increases by

42

Page 42
Image 42
Raypak 850, 300 operating instructions Preparation, Start-Up, Blower Check