Fig. 9: Single Domestic Hot Water Heater and Storage
Tank
NOTE: If local codes require a vacuum relief valve, acquire one locally and install per valve manufacturer’s instructions.
Potable Water and Space Heating
CAUTION: When this heater is used for both potable water and space heating, observe the following to ensure proper operation.
1.All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water.
2.Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
3.If the heater will be used to supply potable water, it shall not be connected to any heating system or components previously used with a
4.When the system requires water for space heating at temperatures higher than 140°F (60°C), a means such as a mixing valve shall be installed to temper the water in order to reduce scald hazard potential.
Fig. 10: Multiple Boilers — Reverse Return,
Primary/Secondary Piping with Indirect DHW
Model |
| Soft | Medium | |||||||
No. | ∆T | gpm | ∆P | MTS | SHL | ∆T | gpm | ∆P | MTS | SHL |
300 | 30 | 19 | 8 | 1.5 | 10 | 20 | 28 | 17 | 1.5 | 20 |
500 | 30 | 31 | 7 | 2 | 8 | 20 | 47 | 16 | 2 | 18 |
850 | 30 | 53 | 17 | 2 | 20 | 20 | 80 | 40 | 2 | 46 |
∆T = Temperature rise, °F.
∆P = Pressure drop through heat exchanger, ft.
SHL = System head loss, ft (based on heater and tank placed no more than 5 ft apart and equivalent length of 25 ft of tubing). gpm = Gallons per minute, flow rate.
MTS = Minimum tubing size.
CAUTION: For scale free operation with Medium water
Table H: Domestic Water Heater Flow Rate Requirements