24” |
SERVICE |
CLEARANCE |
24” |
SERVICE |
CLEARANCE |
Heater | Min. Clearances | Recommended |
from Combustible | Service | |
Side | Surfaces | Clearances |
Rear | 24” | 24” |
Right Side | 0” | 0” |
Left Side | 0” | 0” |
Top | Unobstructed | 24” |
Front | Open | 24” |
Vent | 12” | 12” |
Termination |
Table E: Clearances — Outdoor Installations
Combustion and Ventilation Air
NOTE: Use of this boiler in construction areas where fine particulate matter, such as concrete or
24” |
SERVICE |
CLEARANCE |
Venting not shown for clarity. Heater must be vented per
instructions in this manual
Fig. 4: Minimum Clearances from Combustible Surfaces — Indoor and Outdoor Installations
Indoor Units
This heater must be supplied with sufficient quantities of
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler and void the warranty. (See the Appendix.)
NOTE: It is recommended that the intake vent be insulated in cold climates to minimize sweating.
9