Installer Menu Items (continued)
Screen No. | Default Information Displayed | Range | Description | |
11 | Reset Min Temp |
| Minimum outdoor reset setpoint temperature | |
95 ºF | Setting | |||
| ||||
12 | Hydronic Min Temp |
| Hydronic minimum temperature | |
90 ºF | Setting | |||
| ||||
13 | Hyd Pump Delay |
| Heater pump delay timing | |
0 min | Setting | |||
| ||||
14 | DHW Priority |
| DHW priority timing | |
30 m | Setting | |||
| ||||
15 | Cascade Addr |
| Heater cascade address, 0 for master, | |
0 | Heater address setting, do not use address 8 | |||
| ||||
16 |
| |||
DHW Thermistor |
| Direct/DHW Thermistor/OFF/Boosterboard | ||
|
| |||
17 |
| Mode selection for | ||
Temperature |
| Temperature (Setpoint) or Fan Speed (Firing rate) | ||
|
| |||
18 | Step Mod |
| Enable or disable step modulation | |
ON | ON/OFF | Setting | ||
| ||||
19 | Temp to Indirect |
| Heater output setpoint for indirect operation | |
180 ºF | Setting | |||
| ||||
20 | WPS Input |
| Factory configured, do not change | |
Flow Switch |
| Low Water Cutoff/Flow Switch/Water Pressure/None | ||
|
| |||
21 | Error Outd Sensor |
| Enable outdoor sensor error reporting | |
OFF | ON/OFF | Setting | ||
| ||||
22 | Max Fan Speed |
| Allows reduction of maximum input rate | |
100% | Setting | |||
| ||||
23 | Cascade Config |
| Cascade or non cascade operation | |
OFF/VIS 3 | All 926/OFF | All 926 for single or multi heater cascade | ||
| ||||
24 | Cascade Rotation |
| Lead boiler rotation time | |
24 hours | Setting | |||
| ||||
25 | Cascad DHW Conf |
|
| |
DHW Entire Cascade |
| DHW Entire Cascade/DHW Master Only | ||
|
| |||
26 | System Pump Freeze |
| Enables system pump (if cascade master and controlling system | |
Protect OFF | OFF to 104 ºF | |||
| pump) when outdoor temp drops below the setpoint. | |||
27 | Sys Sense Fault |
| Enable system sensor error reporting | |
ON | ON/OFF | Setting | ||
| ||||
28 | Freeze Protect |
| Heater freeze protection, enables heater pump at return temps | |
ON | ON/OFF | |||
| below 44 ºF, fires heater if temps drop below 37 ºF. | |||
29 | DHW Demand Start |
| Max for normal DHW operation, Min for low fire start DHW | |
Maximum |
| Maximum/Minimum | ||
|
| |||
30 | Extra Boiler |
| Off if no extra boiler, 100 for extra on/off boiler. | |
OFF | Setting | |||
| ||||
31 | Sing Boil Casc |
| Enable single boiler cascade for single boiler primary/secondary | |
OFF | ON/OFF | |||
| operation with a system sensor | |||
32 | Maintenance Mode |
| Installers only - Enable maintenance mode alert by date or running | |
OFF | OFF/RH/Date | |||
| hours | |||
33/34/35 | Maintenance Setting |
| Running hours or date | |
|
|
| ||
|
|
|
| |
36 | Maintenance Setting |
| Telephone numbers | |
| Will not display if all 0's | |||
|
|