Flow Switch
This standard,
Fig. 27: Flow Switch
Low Water Cut-Off (Optional)
The optional low water
Fig. 28: Low Water
High & Low Gas Pressure Switches (Optional)
The optional low gas pressure switch connection mounts upstream of the gas valve (on the inlet flange to the gas valve) and is accessible through the remov- able access panels on the rear of the boiler to reset the gas pressure switch, as necessary. It is used to ensure that sufficient gas pressure is present for prop- er valve/regulator performance. The low gas pressure switch automatically shuts down the boiler if the gas supply drops below the factory setting of 3.0 in. WC for natural gas or propane gas.
The optional high gas pressure switch connection mounts
Operation of either the High or Low Gas Pressure Switch will turn on an LED inside the switch housing. Push the top of the plastic switch housing as shown in Fig. 29 to reset a tripped pressure switch. The LED will go out when the switch is reset.
Fig. 29: High/Low Gas Pressure Switch
Blocked Vent Switch
This heater is equipped with a blocked vent pressure switch to prevent the operation of the boiler when too much of the vent is blocked. This switch is located on the left side of the heater near the left rear corner.
Fig. 30: Blocked Vent Switch
33