MAINTENANCE
Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and maintenance must be performed to ensure maximum operating efficiency.
Maintenance as outlined below may be performed by the owner.
Daily
1.Check that the area where the boiler is installed is free from combustible materials, gasoline, and other flammable vapors and liquids.
2.Check for and remove any obstruction to the flow of combustion or ventilation air to boiler.
Monthly
1.Check for piping leaks around pumps, mixing valves, relief valves, and other fittings. If found, repair at once. DO NOT use
2.Visually inspect burner flame.
3.Visually inspect venting system for proper func- tion, deterioration or leakage.
4.Visually inspect for proper operation of the con- densate drains in the venting, and the internal condensate trap. Clean trap as necessary. If leaks are observed, repair at once.
5.Check air vents for leakage.
Yearly (Beginning Of Each Heating Season)
Schedule annual service call by qualified service agency.
1.Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal.
2.Visually inspect venting system for proper func- tion, deterioration or leakage. Ensure that condensate drain is inspected and ensure that
condensate is being directed to appropriate con- densate management system or drain, as required by local codes.
3.Check that area is free from combustible materi- als, gasoline, and other flammable vapors and liquids.
4.Check for and remove any obstruction to the flow of combustion or ventilation air to boiler.
5.Follow
6.Visually inspect burner flame. It should be light blue at full input. Remove and visually inspect direct spark igniter and sensor for damage, crack- ing or debris
7.Check operation of safety devices. Refer to manu- facturers’ instructions.
8.Follow
9.To avoid potential of severe burn, DO NOT REST HANDS ON OR GRASP PIPES. Use a light touch; return piping will heat up quickly.
10.Check blower and blower motor.
11.Check for piping leaks around pumps, relief valves and other fittings. Repair, if found. DO NOT use
Periodically
1.Check relief valve. Refer to manufacturer’s instructions on valve.
2.Test low water
Preventive Maintenance Schedule
The following procedures are recommended and are good practice for all XFyre installations.
Daily
1.Check gauges, monitors and indicators.
2.Check instrument and equipment settings. (See “Post
49