NOTE: While a drain connection is required in the vent of all XFyre installations, the drain can be ac- complished in several different ways. The figures in this manual show the drain in a vent tee, however, this can also be accomplished using an inline collec- tor for condensing stacks or an inline vertical or horizontal collector available from several of the listed vent manufacturers.
CAUTION: This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system will void all warranties on this boiler.
Installation
These installations utilize the
The total length of the horizontal
equivalent ft, an appropriately sized
The vent and air intake runs should be balanced to provide approximately the same equivalent length. The vent cap and air intake elbow are not considered in the overall length of the venting system.
The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:
1.The vent must be installed with condensate drains as directed by the vent manufacturer.
2.The vent must be installed with a slight upward slope of not less than 1/4 inch per foot of horizon- tal run to the vent terminal.
Termination
The vent cap MUST be mounted on the exterior of the building. The vent cap cannot be installed in a well or below grade. The vent cap must be installed at least 1 ft above ground level and above normal snow levels. Only
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
| Model No. |
| Size |
| Approved Intakes |
| Approved Plastic |
| Approved SS Terminals |
|
|
|
|
|
|
| |||||
|
| (in.) |
|
| Terminals |
|
| |||
| 300 |
| 4 |
| PVC 90° Elbow, |
| 4" PVC Tee, Sch |
| FasNSeal FSTT4, |
|
|
|
|
| Sch 40 |
|
|
| |||
| 500 |
|
|
|
| |||||
|
|
|
| Galvanized 90° |
| 40* |
|
|
| |
|
|
|
|
| Elbow SS 90° |
| 6" PVC Tee, Sch |
|
|
|
| 850 |
| 6 |
|
|
| FasNSeal FSTT6, Heat Fab 9690TEE |
| ||
|
|
| Elbow |
| 40* |
|
| |||
| *Must be | materials in Canada. |
|
|
|
|
| |||
|
|
|
|
| Table N: Horizontal Vent and Air Intake Terminals |
29