Ignition Module
When additional heat is needed, the combustion air blower starts to purge air from the combustion cham- ber for about 15 seconds. On
The optional
High Limit (Manual Reset)
Fig. 32: Ignition Module
proving switch closes and the igniter is energized. To ensure safe operation, the gas valve cannot open until the igniter is verified. The main burner is automatically lit when the device is powered and
The standard ignition module will attempt to light three times before locking out. To reset it, turn off power to the heater, wait 30 seconds and
| Code | Condition |
|
|
|
|
|
| On | System OK; |
|
| No faults present |
| |
|
|
| |
|
|
|
|
| Off | Possible control fault; |
|
| Check power |
| |
|
|
| |
|
|
|
|
| 1 Flash | Low air pressure, brief |
|
| flashing normal on |
| |
|
|
| |
|
|
|
|
| 2 Flashes | Flame in combustion |
|
| chamber; No call for heat |
| |
|
|
| |
|
|
|
|
| 3 Flashes | Ignition lockout |
|
|
|
|
|
| 4 Flashes | Low igniter current |
|
|
|
|
|
| 5 Flashes | Low 24 VAC, check control |
|
| supply voltage |
| |
|
|
| |
|
|
|
|
| 6 Flashes | Internal fault; |
|
| Replace module |
| |
|
|
| |
|
|
|
|
Table N: Ignition Module Diagnostic LED Codes
Fig. 33: High Limit (Manual Reset)
The heater is equipped with a manual reset high limit temperature device. Push the reset button and adjust the setting to 40 - 50°F above desired operating tem- perature.
Flow Switch
Fig. 34: Flow Switch
This
Operating Control
The heater may be equipped with different types of operating controls. Consult the individual control data