Raypak HD401, HD101 Electrical Power Connections, Gas Pressure Regulator, Gas Supply Pressure

Models: HD101 HD401

1 48
Download 48 pages 21.74 Kb
Page 18
Image 18
Gas Pressure Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 13: Sediment Trap Orientation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Do not use Teflon tape on gas line pipe

 

 

 

 

 

Gas Pressure Regulator

 

 

 

 

thread. A pipe compound rated for use with gas

 

 

 

 

 

The gas valve pressure regulator(s) on the heater are

 

systems is recommended. Apply sparingly only on

 

 

 

 

 

 

male pipe ends.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nominally preset at 3 in. WC for natural gas, and 10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in. WC for propane gas manifold pressure. The pres-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Support gas supply piping with

 

 

 

 

 

sure at the gas valve outlet tap, measured with a

 

hangers, not by the heater or its accessories. Ensure

 

 

 

 

 

manometer, while in operation should be as indicated

 

the gas piping is protected from physical damage

 

 

 

 

 

in Table G. If an adjustment is needed, turn the adjust-

 

and freezing where required.

 

 

 

 

 

 

 

ment screw clockwise to increase pressure or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

counter-clockwise to decrease pressure.

 

Gas Supply Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Power Connections

 

A minimum of 4 in. WC and a maximum of 10.5 in. WC

 

 

 

 

 

upstream gas pressure is required under load and no

 

 

 

 

Installations must follow these codes:

 

load conditions for natural gas. A minimum of 11 in.

 

 

 

 

 

WC and a maximum of 13 in. WC is required for

 

 

 

 

· National Electrical Code and any other national,

 

propane gas. The gas pressure regulator supplied on

 

 

 

 

state, provincial or local codes or regulations hav-

 

the heater is for low pressure service. If upstream

 

 

 

 

ing jurisdiction

 

pressure exceeds 14 in. WC, an intermediate gas

 

 

 

 

· Safety wiring must be N.E.C. Class 1

 

pressure regulator, of the lockup type, must be

 

 

 

 

· Heater must be electrically grounded as required

 

installed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by N.E.C.

 

When connecting additional gas utilization equipment

 

 

 

 

· In Canada, C22.1

 

to the gas piping system, the existing piping must be

 

 

 

 

The heater is wired for 120 VAC, less than 12 AMPS.

 

checked to determine if it has adequate capacity.

 

 

 

 

The voltage is indicated on the tie-in leads. Consult the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Type

 

 

 

 

wiring diagram shipped with the heater in the instruc-

 

 

Firing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve

 

 

 

Natural

 

LP/Propane

 

 

 

 

tion packet. The remote tank control stat, thermostat,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stage

 

 

 

 

 

 

 

 

 

 

 

 

+/- 0.1"WC

 

+/- 0.1"WC

 

 

 

 

or electronic heater control as applicable, may be con-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nected to stage selector terminal (See wiring diagram).

 

Hi-Fire

 

 

 

 

Invensys

 

 

3.3" WC

 

 

 

 

 

 

 

24 Volts are supplied to this connection through the

 

 

 

 

 

Honeywell or

 

 

3.1" WC

 

9.6" WC

 

 

 

 

heater transformer. DO NOT attach line voltage to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

White-Rodgers

 

 

 

 

 

 

 

the stage connections. Before starting the heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Invensys

 

 

1.2" WC

 

 

 

 

 

 

 

check to ensure proper voltage to the heater and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lo-Fire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pump.

 

 

 

 

 

Honeywell or

 

 

1.4" WC

 

3.6" WC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING: Connecting line voltage to the stage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

White-Rodgers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection terminal block will cause damage to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit that is not covered by warranty.

 

 

 

 

 

 

 

Table

G: Pressure at

Gas Valve

 

Outlet Tap

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 