Raypak HD401, HD101 Hydronic Heating, Hydrostatic Test, Low Temperature System, Pump Selection

Models: HD101 HD401

1 48
Download 48 pages 21.74 Kb
Page 14
Image 14
Hydrostatic Test

Hydrostatic Test

Unlike many other types of heaters, Raypak heaters do not require hydrostatic testing prior to being placed in operation. The heat exchanger has already been factory-tested and is rated for 160 PSI maximum oper- ating pressure. However, Raypak does recommend hydrostatically testing the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol-based antifreeze. Raypak recom- mends conducting the hydrostati c test before connecting gas piping or electrical supply.

Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.

1.Connect fill water supply. Fill heater with water (be sure bleed valve is open). When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, being sure to eliminate any entrapped air by using high point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.

2.Make sure constant gauge pressure has been maintained throughout test.

3.Check for leaks. Repair if found.

Low Temperature System

Heater requires minimum inlet temperature of 105°F. Consult the following sections for piping details.

Temperature & Pressure Gauge

The temperature and pressure gauge is shipped loose for field installation.

Hydronic Heating

Pump Selection

In order to ensure proper performance of your boiler system, you must install a properly sized pump. Raypak recommends using a 20°F ∆T as design ∆T. (∆T is the temperature difference between the inlet and outlet water when the heater is firing at full rate). If a ∆T other than 20°F is necessary, see Table E for flow rate requirements.

Pressure Drop in Feet of Head Feedwater Regulator

Raypak recommends that a feedwater regulator be installed and set at 12 psi minimum pressure at the highest point of system. Install a check valve or back flow device upstream of the regulator, with a manual shut off valve as required by local codes.

 

 

 

 

 

 

 

 

 

 

Model

Input

Output

10°F ∆T

20°F ∆T

30°F ∆T

Min. Flow

 

Max. Flow

 

No.

MBTUH

MBTUH

gpm

∆P (ft)

gpm

∆P (ft)

gpm

∆P (ft)

gpm

∆P (ft)

∆T

gpm

∆P (ft)

∆T

HD101

100

85

17

1.3

 

 

 

 

13

0.7

14

44

8.8

4

HD151

150

128

26

3.0

13

0.7

 

 

13

0.7

20

44

8.8

6

 

 

HD201

199

169

34

5.3

17

1.3

 

 

13

3.4

27

44

8.9

8

 

 

HD251

250

213

44

9.2

21

2.1

14

1.0

13

0.7

34

44

9.2

10

HD301

299

254

 

 

25

3.1

17

1.4

13

0.8

40

44

9.4

12

 

 

HD401

399

335

 

 

34

5.6

22

2.5

17

1.4

40

44

9.8

15

 

 

*Flow switch will not activate at less than 12 gpm.

NOTE: Basis for minimum flow — 13 gpm or 40°F ∆T maximum flow — gpm, except for header.

Table E: Heater Rates of Flow and Pressure Drops

14

Page 14
Image 14
Raypak HD401 Hydronic Heating, Hydrostatic Test, Low Temperature System, Temperature & Pressure Gauge, Pump Selection