HD101-HD401 Troubleshooting

HD101-HD401 Troubleshooting

Step 1

Step 2

Step 3

Step 4

Does the main power switch provide

NO

 

Check the switch, transformer

power to the green power LED?

 

 

and/or line voltage

 

YES

 

Is Disable connection intact?

NO

Reattach.

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

Is there a Call For Heat?

 

NO

 

Is temperature controller

NO

 

 

 

 

installed?

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Does the Pump come on?

NO

Is there 120VAC at the pump or

NO

 

 

pump relay contacts?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Does the combustion air

 

NO

Is there120 VAC at the blower,

NO

 

 

between the red & white leads?

 

blower come on?

 

 

 

 

 

 

 

 

 

 

 

 

NO

Check safeties, I.E. Flow switch, high

 

 

 

 

 

YES

 

 

 

 

 

limit, vent switch, thermostat, etc.

 

 

 

 

 

 

 

Install.

Check and correct power

connections at main terminal block, circuit breaker panel or pump relay.

Check and correct power

connections at main terminal block, ignition module, circuit breaker panel or blower relay.

Step 5

Step 6

Step 7

Is 24VAC at the NO side of

NO

the air pressure switch?

 

YES

 

Is 24VAC at PS on ignition module?

Is connecting plug secure?

YES

Does igniter prove?

NO

 

Is blower pressure setting correct? Should be about 0.5” W.C. (low speed)

YES

Replace low air pressure switch.

NOCorrect wiring.

Is Amp draw during heat-

NO

up for HSI greater than

 

3.1 Amps?

 

NO

Correct the blower

shutter setting.

 

NO

Is the air filter or

air intake blocked?

YES

Remove blockage and/or replace filter

Replace HSI

YES

YES

 

 

NO

Is air switch bouncing?

 

YES

 

 

 

 

 

 

 

Step 8

Step 9

Step 10

Is the flame sensor signal to the ignition

NO

Is inlet gas supply pressure

 

 

NO

Correct inlet gas supply pressure

 

 

 

module greater than 1 Micro Amp (µA) DC?

 

correct?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

YES

 

 

 

NO

 

 

 

 

Adjust manifold gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is manifold gas

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure correct?

Replace gas valve

 

 

Does the unit run longer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than 10 seconds?

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

Does the unit run at least

YES

 

Does the air pressure

 

Replace high air pressure switch

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

YES

 

 

5 seconds?

 

 

 

reach 0.9” W.C.?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

NO

 

Is the air filter or air

NO

Replace blower

 

 

 

 

Is the polarity of incoming

 

 

 

 

 

 

 

 

 

 

 

 

 

The unit is okay

 

 

 

 

 

 

intake blocked?

 

 

 

 

 

power supply correct?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

YES

 

 

 

 

 

Remove blockage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct supply wiring

 

 

 

 

 

 

 

 

 

and/or replace filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Call our Technical Service Department

 

 

 

 

Is sensor

 

probe grounded?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

YES

Replace Sensor

 

 