Regency E21-NG2 Installation Checklist, Minimum Fireplace Clearances, This includes, Depth

Models: E21-NG2 E21-LP2

1 32
Download 32 pages 58.92 Kb
Page 7
Image 7
INSTALLATION

INSTALLATION

POLICY FOR SOLID FUEL BURNING & FACTORY BUILT FIREPLACES

The Regency® E21 may be installed and vented intoanysolidfuelfireplacethathasbeeninstalled in accordance with the National, Provincial and local building codes and is constructed of non- combustible materials.

1)Installer must mechanically attach the sup- plied label to the inside of the fi rebox of the fi replace into which the gas fi replace insert is installed.

"WARNING:This fireplace has been converted for use with a gas fi replace insert only and cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fi replace re-approved by the authority having jurisdiction."

2)Do not cut any sheet-metal parts of the

replace, in which the gas fi replace insert is to be installed.

3)Ifthefactory-builtfireplacehasnogasaccess hole(s) provided, an access hole of 1-1/2" (37.5mm) or less may be drilled though the lowersidesorbottomofthefireboxinaproper workmanship like manner. This access hole must be plugged with a non-combustible insulation after the gas supply line has been installed.

4)Thefireplacefluedampercanbefullyblocked open or removed for installation of the gas

replace insert.

5)The fi replace and fi replace chimney must be clean and in good working order and constructed of non-combustible materials.

6)The chimney cleanouts must fi t properly.

7)Refractory (fi rebricks), glass doors, screen rails, screen mesh and log grates can be removed from the fi replace before installing the gas fi replace insert.

8)Smoke shelves, shields and baffles may be removedifattachedbymechanicalfasteners. If any part is removed it must not weaken the structural integrity of the factory built.

9)Trim panels or surrounds shall not seal ventilation openings in the fi replace.

INSTALLATION

CHECKLIST

1)Locate your appliance. Refer to the "Clear- ances to Combustibles" and "Minimum Fireplace Clearances" sections.

2)Make gas and electrical connections. Refer to the "Gas Connection" section.

Test the pilot. Must be as per diagram in the "Valve Description" section.

3)Install Flue Connector. Refer to the "Flue Connector Installation" section.

4)Install vent. Refer to the "Venting" section.

5)Test Gas pressure. Refer to the "Gas Pipe Pressure Testing" section.

Check aeration. Refer to the "Gas Insert Aeration System" section.

6)Test for fl ue spillage. Refer to the "Test for Flue Spillage" section.

7)Install standard and optional features. Refer to the following sections where applicable:

a.Brick Panel

b.Faceplate & Trim

c.Flush Glass

d.Flush Louver

e.Bay Front

f.Full Screen Doors

g.Remote Control

h.Wall Switch

i.Wall Thermostat

8)Final check. Refer to the "Final Check" section.

Before leaving this unit with the customer, the installer must ensure that the appliance is

ring correctly and operation fully explained to customer.

This includes:

1)Clocking the appliance to ensure the correct fi ring rate (rate noted on label) after burning appliance for 15 minutes.

2)Ifrequired,adjustingtheprimaryairtoensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

3)Ensure that the appliance is venting correctly.

CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.

MINIMUM FIREPLACE

CLEARANCES

Diagram shows the minimum fi replace opening required to be able to install the Regency® gas fi replace insert.

Note: If you are installing the Molded Faceplate, the minimum fireplace dimensions are as follows:

Width (at front):

29-1/8" (740mm)

Depth:

15" (381mm)

Height:

18-5/8" (473mm)

Regency® E21-2 Gas Fireplace Insert

7

Page 7
Image 7
Regency E21-NG2 Installation Checklist, Minimum Fireplace Clearances, This includes, Width at front, Depth, Height