REQUIREMENTS

MA Code - CO Detector

(for the State of Massachusetts only)

5.08: Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:

1.The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2.The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Regency® L676E Direct Vent Gas Fireplace

5

INSTALLATION

Page 5
Image 5
Regency L676E-NG, L676E-LP installation manual Requirements, MA Code CO Detector

L676E-LP, L676E-NG specifications

Regency L676E-LP and L676E-NG are two remarkable gas fireplaces designed to elevate any living space with their blend of efficiency, aesthetics, and innovative technology. These models stand out with their versatile design, suitable for both new and existing homes, while offering homeowners an exceptional heating experience.

Both the L676E-LP (liquid propane) and L676E-NG (natural gas) fireplaces showcase a stylish contemporary design that fits seamlessly into modern and traditional decors alike. With a sleek and elegant appearance, these fireplaces serve as a stunning focal point in any room, creating a cozy ambiance while efficiently warming the space.

One of the key features of the L676E series is its high-efficiency rating. These gas fireplaces are engineered to produce substantial heat while minimizing energy consumption. Equipped with advanced energy-efficient technology, they provide a significant reduction in utility costs compared to traditional heating methods. The L676E models also come with an impressive heat output, making them suitable for larger areas, effectively maintaining a comfortable environment during colder months.

The L676E fireplaces are built with a powerful burner system that ensures even heat distribution throughout the room. The innovative technology allows for adjustable flame heights, enabling users to customize the intensity of the fire to suit their mood. The clean-burning design also contributes to an environmentally-friendly experience, producing minimal emissions and reducing the carbon footprint.

Another standout characteristic is the ease of use and convenience offered by both models. Featuring an intuitive remote control system, users can adjust settings effortlessly. The option for thermostat control further enhances comfort, allowing the fireplace to maintain a consistent temperature automatically.

Safety is paramount in the design of the L676E-LP and L676E-NG fireplaces. They are equipped with advanced safety features, including an automatic shutdown system and a protective glass front to prevent accidental burns. Additionally, their durable construction ensures long-lasting performance and reliability.

In summary, the Regency L676E-LP and L676E-NG gas fireplaces merge cutting-edge technology with elegant design. Their high efficiency, impressive heating output, and safety features make them a valuable addition to any home, providing both comfort and style. Whether for new construction or retrofitting an existing space, these models represent an ideal choice for homeowners seeking a blend of functionality and sophistication.