Roberts Gorden CGTH-40, CGTH-30 5.5Cox Geelen Vertical Venting, Vertical Venting Configurations

Models: CGTH-40 CGTH-50 CGTH-30

1 58
Download 58 pages 49.39 Kb
Page 35
Image 35
5.5Cox Geelen Vertical Venting

SECTION 5: VENTING INSTALLATION

5.5Cox Geelen Vertical Venting

FIGURE 28: Vertical Venting ConfigurationsWARNING

Carbon Monoxide Hazard

Heater must be exhausted outside. Use materials supplied.

This heater needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.

Failure to follow these instructions can result in death or injury.

After the heater has been properly suspended in accordance with the preceding headings of this sec- tion, proceed to install the venting as described below. Be sure to observe the General Venting Guidelines on Page 14, Section 4.5.

FIGURE 28: Vertical Venting Configurations

 

VERTICAL

 

 

 

Roof

Roof

 

 

 

Terminal

 

 

 

 

 

 

30” (762 mm)

90506008

 

 

 

 

 

 

 

minimum

 

 

 

 

above roof

 

 

 

 

 

Storm

 

 

 

 

Collar

 

 

 

 

 

Vent

 

 

 

 

Clamp

90506003

 

 

 

 

 

 

90506004

A

 

 

90506005

 

 

 

 

 

90506001

90506012

Burner

 

 

B

 

 

 

Use Table 2 to select lengths for A & B

Table 2: Components

Part Number

Description

90506001

Elbow 90°

 

90506003

Concentric Flue

10" (254 mm)

90506004

Concentric Flue

20" (500 mm)

90506005

Concentric Flue

39" (1000 mm)

90506008

Roof Terminal

50.5" (1283 mm)

90506012

Burner/Vent Adapter

1.Using a saw, cut an appropriate size clearance hole in the roof to accommodate the vertical run of vent pipe and the vent termination (minimum 5" [125 mm]).

2.Install the vent adapter (P/N 90506012) and secure with #8 x 3/8" sheet metal screws as shown on Page 28, Figure 26.

3.Measure the distance to the center of the hole from the vent adapter. Note this dimension here

_________. If the concentric vent has to be cut, use the following guidelines:

A.Subtract 1.5" (38 mm) to allow for the elbow and both joints.

B.Separate the 3" (80 mm) and the 5" (125 mm) vent by pulling the 3" (80 mm) vent out from the end with the internal silicone gasket. Remove the internal spring from the non-sili- cone gasket end of the 5" (125 mm) vent.

C.Always cut the 3" (80 mm) and 5" (125 mm) vent separately to avoid damage.

D.Always cut from the non-silicone gasket end and deburr thoroughly.

4.Install a 4-7" EPDM storm collar (P/N 90506015) following the instruction below:

A.Slide storm collar down over lower section of the vertical vent. Water can be used as a lubricant. Apply silicone sealant on under- side of flange. Turning back flexible flange makes this simple.

B.Press pipe flashing into contours of roof panel configuration. If there is a sharp angle in the panel, a blunt tool can be used to press the flashing into place.

C.Lower roof terminal (P/N 90506008) through the 5" (125 mm) hole. From the inside ensure the vent is square. Secure the vent clamp to the inside of the roof. See Figure 28.

D.Apply silicone sealant between base and roof. Drill and fasten flashing to surface. Use a blunt tool to press base into sharp corners of valleys while drilling; and against to insert rivet or screw.

E.Follow the sequence: drill two holes on oppo- site sides of aluminum base through sheet.

29

Page 35
Image 35
Roberts Gorden CGTH-40, CGTH-30 5.5Cox Geelen Vertical Venting, Vertical Venting Configurations, Part Number, Description