Roberts Gorden CGTH-30, CGTH-50 Burner Cycles On And Off Too Quickly, Possible Cause, Try this

Models: CGTH-40 CGTH-50 CGTH-30

1 58
Download 58 pages 49.39 Kb
Page 45
Image 45
BURNER CYCLES ON AND OFF TOO QUICKLY

SECTION 9: TROUBLESHOOTING

BURNER DOES NOT STAY LIT

 

Possible Cause

Try this....

 

 

Damaged wires between DSI

Replace wires as required.

module and sensing electrode.

 

 

 

Faulty DSI module.

Replace DSI module.

 

 

Cracked ceramic at the

Replace electrode.

sensing electrode.

 

 

 

Recirculation of

Check that the 3” (80 mm) inner vent pipe is completely sealed.

exhaust gases.

 

 

BURNER CYCLES ON AND OFF TOO QUICKLY

Possible Cause

Try this....

 

 

Anticipator setting on

Adjust the anticipator setting to 0.6. See Page 20, Figure 12.

the thermostat is too low

 

.18

 

.2

.9

 

 

.7

 

.5

.25

.4

 

 

.3

39

Page 45
Image 45
Roberts Gorden CGTH-30, CGTH-50, CGTH-40 service manual Burner Cycles On And Off Too Quickly, Possible Cause, Try this