SECTION 7: HEATER INSTALLATION

SECTION 7: HEATER INSTALLATION

SECTION 7: HEATER INSTALLATION

on Page 14, Figure 12. WARNING

Suspension Hazard

Burner is secured to burner tube by bolts and lockwashers.

Hang heater with materials with a minimum working load of 75 lbs (33 kg).

Failure of the supports can result in death, injury or property damage.

To ensure your safety, and comply with the terms of the warranty, all units must be installed in accordance with these instructions.

The gas or the electrical supply lines must not be used to support the heater.

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in a location that is readily accessible for servicing.

The heaters must be installed in accordance with clearances to combustibles as indicated on the rating plate and in this instruction manual.

The minimum and maximum gas inlet pressures must be maintained as indicated on the rating plate. Typical installation configurations are shown

on Page 14, Figure 12.

Expansion and contraction of the tube dictates that the minimum suspension lengths in the table on Page 14, Figure 12 be maintained.