3. Installation

3.2.3. Chassis Ground Connection

The RX1501 chassis ground connection, shown in Figure 3.12, “Chassis Ground Connection”, uses a #10-32 screw. It is recommended to terminate the ground connection in a #10 ring lug. Torque on the chassis ground connection should not exceed 30 in-lbs (3.4 Nm).

Figure 3.12. Chassis Ground Connection

3.2.4. AC Power Supply Wiring Example

Figure 3.13. Wiring for Single AC Power Supply (HIP module shown)

For 125/230VAC rated equipment, a appropriately rated AC circuit breaker must be installed.

It is recommended to provide a separate circuit breaker for each power supply module.

Equipment must be installed according to applicable local wiring codes.