2. Fix the indoor unit.
(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.
• If you mount the plate to a concrete wall using plastic anchors, make sure that gaps between the wall and the plate, created by projected anchor, is less than 20 mm.
Plastic |
|
|
Anchor |
| Wall |
| < 20 mm | |
|
|
(1) | Determine the positions of the wooden uprights to be | (1) |
| |
| attached to the window frame. | (2) | Fix the plate hanger on two studs. | |
(2) | Attach the wooden uprights to the window frame giving | |||
|
| |||
| attention to the weight of the indoor unit. |
|
| |
(3) | Attach the installation plate to the wooden upright using |
|
| |
| tapping screws. |
|
|
•Search for other spots if there are less than two studs, or the distance between the studs are from the
plate hanger.
•Fix the installation plate without inclining to one side.
•Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not
strong enough to withstand the product weight, the unit could fall and cause injury.
Connecting the assembly cable
Model | Power cable | Interconnection cable | Type GL |
|
|
|
(Outdoor Unit) |
|
|
| |||
|
|
| ||||
|
|
|
|
|
3G, 1.0 mm2
10/13 3G, 1.5 mm2
3G, 1.0 mm2
18/24 3G, 2.5 mm2
• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.
Connecting the cable
Electrical work
1)For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the ‘wiring regulations’ of the Local wiring regulations.
2)Tighten the terminal block screw to under 1.2 N.m (12 kgf.cm).
3)Precautions when connecting terminal blocks of the indoor unit
Before connecting, make sure the connecting part of the terminal socket is facing upwards.
Upside down | The terminal socket | There is no ring terminal | |
is damaged. | to cover the wire. | ||
|
34
MAX_