Purging the indoor unit

The indoor unit is supplied with inert gas (nitrogen).

If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.

1.Unscrew the caps at the end of each pipe.

All inert gas exhausts from the indoor unit.

• To prevent dirt or foreign substances from getting into the pipes during

installation, do NOT remove the caps completely until you are ready to

 

 

connect the pipes.

 

 

• The remaining air in the Refrigeration cycle, which contains moisture,

Pipes

Unscrew the caps

 

 

may cause malfunction on the compressor.

Always contact the service center or a professional installation agency for product installation.

Cutting or extending the pipe

The length of the pipe can be:

Extended up to : see table page 30

Shorten up to: see page 30

If you need a pipe longer than 5 meters:

• You must extend the assembly cable.

• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

1.

2.If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe (see below examples of correct and incorrect cut edges).

Pipe

Oblique

Rough

Burr

cutter

 

 

 

Pipe

3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

4.

 

90°±2°

Outer Diameter (D)

Depth (A)

Flaring Size (B)

 

B

ø6.35 mm

1.3 mm

8.7

- 9.1 mm

 

ø9.52 mm

1.8 mm

12.8 - 13.2 mm

 

 

 

 

ø12.70 mm

2.0 mm

16.2 - 16.6 mm

 

R0.4~0.8

ø15.88 mm

2.2 mm

19.3 - 19.7 mm

Pipe

Flare

 

 

 

 

37