Cutting or extending the pipe

5.

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.

applying the following torque:

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

 

Torque

N•m

 

(kgf•cm)

 

 

ø6.35 mm

14 ~ 18

 

140 ~ 180

ø9.52 mm

34 ~ 42

 

350 ~ 430

ø12.70 mm

49 ~ 61

 

500 ~ 620

ø15.88 mm

68 ~ 82

 

690 ~ 830

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 40.

• Tighten thenut with torque wrench according tomethod.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

5 cm less

Keep a clearance of at least

5 cm between the end of the drain hose and the ground.

The drain hose must NOT slant upwards.

Ditch

Do not place the end of the drain hose in a hollow.

The end of the drain hose must NOT be placed under water.

The drain hose must not be bent.

After completing the installation of the drain hose, pour water into the drain pan to check whether the hose is well drained.