Samsung ACC2800C, UCC2800C, UCC2400C, ACC2400C Drain Hose Installation, Indoor, Unit

Models: ACC2400C ACC2800C UCC2400C UCC2800C

1 70
Download 70 pages 23.81 Kb
Page 42
Image 42
Drain Hose Installation

Drain Hose Installation

Indoor Drain tube outlet

 

Insulation drain sub

Indoor

Band(Not supplied)

Unit

 

Adhesives UnitManual background

Insulation drain pipe

Insulation cover drain

CAUTION

Must fit tightly against body without any gap.

No gap

Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside.

1Insert the flexible hose to the drain tube outlet, if necessary.

Note Attach the drain hose to the drain tube outlet with the adhesives to prevent water leaks, then secure the hose with a band etc..(The band is not supplied with the air conditioner.)

2Install the drain hose so that its length can be as short as possible. Internal diameter of the drain hose should be the same or slightly bigger than the external diameter.

Inner diameter of the drain hose

Flexible hose is connected

Flexible hose is not connected

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

32mm/1

inch(Outer diameter)

 

 

27mm/1inch(Outer diameter)

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note Give a slightly slant to the drain hose for proper drainage of condensate.

Secure the drain hose with the band joint and the cable-tie not to be separated from the unit.

3Wrap the drain hose with the insulation drain as shown in figure and secure it.

Note When connecting the drain hose without the flexible hose, you should attach it to the drain tube outlet with adhesives and tapes to prevent water leaks.

CAUTION

Check that the indoor unit is level with the ceiling by using the leveler.

Do not install air bleeding tubes, as this may cause water to spray from the drain tube outlet.

If it is necessary to increase the height of the drain hose somewhat, the portion directly after 30cm/1ft. If it is raised higher than 50cm/1 85 ft , there can be water leaks.

Air bleeder

300mm(12")or less

1~1.5m (3~5ft)

 

 

 

 

 

 

Band joint

Flexible hose

Ceiling

Ceiling

55 200mm( 8 ft) 550mm(18 ft) or less

ft) or less

 

7

16

 

(2

 

 

750mm

 

 

 

 

 

 

 

 

 

Do not give the hose and upward gradient after the connection port.

This will cause water to flow backwards when the unit is stopped, resulting in water leaks.

Upward gradient

Do not apply force to the piping on the unit side when connecting the drain hose. The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible.

Support pieces

1~1.5m(3~5ft)

1/100 or more

Ceiling

Ceiling

E-42