Drain Hose Installation
Drain tube outlet
| Insulation drain sub | |
Indoor | Band(Not supplied) | |
Unit | ||
|
Adhesives
Insulation drain pipe
Insulation cover drain
CAUTION
Must fit tightly against body without any gap.
No gap
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside.
1Insert the flexible hose to the drain tube outlet, if necessary.
Note ◆ Attach the drain hose to the drain tube outlet with the adhesives to prevent water leaks, then secure the hose with a band etc..(The band is not supplied with the air conditioner.)
2Install the drain hose so that its length can be as short as possible. Internal diameter of the drain hose should be the same or slightly bigger than the external diameter.
◆ Inner diameter of the drain hose
Flexible hose is connected | Flexible hose is not connected | |||||||||||
|
|
|
|
|
| 1 |
|
|
|
|
| |
|
|
|
|
| 32mm/1 | inch(Outer diameter) |
|
| 27mm/1inch(Outer diameter) | |||
|
|
|
|
| 4 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Note ◆ Give a slightly slant to the drain hose for proper drainage of condensate.
◆Secure the drain hose with the band joint and the
3Wrap the drain hose with the insulation drain as shown in figure and secure it.
Note ◆ When connecting the drain hose without the flexible hose, you should attach it to the drain tube outlet with adhesives and tapes to prevent water leaks.
CAUTION
Check that the indoor unit is level with the ceiling by using the leveler.
Do not install air bleeding tubes, as this may cause water to spray from the drain tube outlet.
If it is necessary to increase the height of the drain hose somewhat, the portion directly after 30cm/1ft. If it is raised higher than 50cm/1 85 ft , there can be water leaks.
Air bleeder
300mm(12")or less | 1~1.5m (3~5ft) | ||||
|
|
|
|
|
|
Band joint
Flexible hose
Ceiling
Ceiling
55 200mm( 8 ft) 550mm(18 ft) or less
ft) or less |
| ||
7 | 16 |
| |
(2 |
|
| |
750mm |
| ||
|
|
|
|
|
|
|
|
Do not give the hose and upward gradient after the connection port.
This will cause water to flow backwards when the unit is stopped, resulting in water leaks.
Upward gradient
Do not apply force to the piping on the unit side when connecting the drain hose. The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible.
Support pieces
1~1.5m(3~5ft) |
1/100 or more
Ceiling | Ceiling |