Connecting Up and Removing Air In the Circuit
The outdoor units is loaded with sufficient
Adding Refrigerant
Refrigerant must be added if the piping measures more than 5 m(16 25 ft) in length (maximum of “A” m/ft). The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist.
☛ | If you have used... | Then... | ||||
|
|
|
|
|
|
|
| More than 5 m(16 | 2 | ft) | “B” of refrigerant | ||
| 5 | |||||
| of the pipes | added for each extra metre. | ||||
|
|
|
|
|
|
|
| Less than 5 m(16 | 2 | ft) | The purge time is normal | ||
| 5 | |||||
| of piping |
| ||||
|
|
|
|
|
|
|
ENGLISH
Model | A |
| B | |
a |
| b | ||
|
|
| ||
ACC2400C | 30m | 40g |
| 50g |
ACC2800C | (100ft) | (0.43oz) |
| (0.54oz) |
For details about the installation situation(a or b), refer to page 44.
1Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
2Referring to the illustration opposite, tighten the flare nut on section B first manually and then with a wrench, applying the following torque.
Outer Diameter | Torque (kgf•cm) | ||
6.35 mm (1/4") | 160(11 | 3 | ft•lb) |
5 | |||
15.88 mm (5/8") | 400(29 ft•lb) |
Outdoor unit |
| Indoor unit |
A | Gas pipe side | C |
B | Liquid pipe side | D |
3Connect the charging hose of low pressure side of manifold gauge to the
packed valve having a service port as shown at the figure.
4 Open the valve of the low pressure side of manifold gauge counter clockwise.
5Purge the air from the system using vacuum pump for about 10 minutes.
◆ Close the valve of the low pressure side of manifold gauge clockwise. |
|
◆ Make sure that pressure gauge show |
|
10 minutes. This procedure is very important in order to avoid gas leak. |
|
◆ Turn off the vacuum pump. | Vacuum |
◆ Remove the hose of the low pressure side of manifold gauge | pump |
maintaining a vacuum. |
|
6 | Set valve cork of both liquid side and gas side of packed valve to the | A(gas) |
| open position. | B(liquid) |
7 | Mount the valve stem nuts and the service port cap to the valve, and |
|
| tighten them at the torque of 183kgf•cm(13ft•lb) with a torque wrench. |
|
8 | Check for gas leakage. |
|
| ◆ At this time, especially check for gas leakage from the |
|
| stem nuts(A port), and from the service port cap. | |
|
| |
|
|