Samsung UPC3240C, APC3240C Connection of Refrigerant Piping, Flare Processing, Pipe Bending

Models: APC3240C UPC3240C

1 36
Download 36 pages 52.33 Kb
Page 30
Image 30
Connection of Refrigerant Piping

INSTALLATION METHOD

Connection of Refrigerant Piping

Flare Processing

1.Cut the pipe using the pipe cutter.

90

Roughness

Burr

Oblique

2. Insert the flare nut into the pipe, and then perform the flare processing.

D

A

Outer Diameter(D)

A

 

 

 

ø

9.52mm(3/8")

1.8mm(1/16")

ø

15.88mm(5/8")

2.2mm(1/8")

Pipe Bending

1.Perform bending of the pipe using the bender which has a specified bending radius.

2.Be sure to take full care to perform bending of the pipe successfully at one time. Bending and unbending the pipe more than twice makes the bending work increasingly difficult.

3.You may use the spring inserted into the gas pipe instead of the bender to bend the pipe.

4.When you bend the pipe using the spring, hold the pipe with both hands to prevent any distortion, and secure a minimum bending radius of more than 100mm(4").

Tightening of Connection Parts

Align the center of the connection piping, and tighten the flare nut by turning it with hand. Then tighten it again using the spanner in the direction as shown in the figure.

Outer Diameter

Tightening Torque

Final Torque

Remarks

 

 

 

 

 

ø

9.52mm(3/8")

400kgcm (28.2ftlb)

450kgcm (31.7ftlb)

 

ø

15.88mm(5/8")

700kgcm (50.6ftlb)

750kgcm (52.8ftlb)

 

❏Flare Processing Spring

E-30

Page 30
Image 30